HeiTel Digital Video GmbH - Quick Installation Guide CamTel SVR
Selected options for
parameter settings
Transmitting
parameters
Model alarm using
Aux in1
CamTel SVR
Parameter settings for the device
After establishing the connection to the device, click on the Setup button to
open the Recorder
settings dialogue window.
User rights: User
■
Network settings: Connections\Network (TCP/IP)
■
Dialling number for alarms: Connections\Phone & IP numbers
■
Arming and alarms: Alarms and sub-points
■
To conclude parameter settings, confirm the change made using OK, so that
the data is transmitted to the device.
For detailed information on device parameterisation, if necessary please
consult Chapter
7 of the CamControl
Testing the alarm
After setting the device parameters, if necessary a test for a correct alarm
should be carried out.
As an example, an alarm via the Aux
on page
17).
This contact, described as the tamper input, is particularly suitable for this,
because an alarm is given regardless of the arming/disarming of the
device. This input is defined as normally opened (NO).
Take the relevant transmission routes into operation.
■
Check the dial-up number(s) for alarms:
■
numbers (if necessary to your receiver PC or to the control station) (see
"Parameter settings for the device" on page
Ensure that the device is not in the alarm status (see "LED Alarm - red" on
■
page
16).
Close the connection from Aux
■
for at least 500 ms.
Check to see whether the alarm is correctly sent to your receiver PC or to
■
the control station.
CamControl
LITE should report "Online/Tamper alarm" in the status line
bottom right in this case:
If the general alarm control input or camera-specific control inputs need to
be checked, ensure without fail that the device has been armed
beforehand.
LITE software manual.
in1 input is described (see "Aux in1"
Connections\Phone & IP
21).
in1 and to the relevant device ground
⊥
21