InstallatIon
assembly
5.
assembly
5.1
Handling
f Observe the handling symbols on the packaging.
5.2
assembly
The appliance can be mounted on the wall or the ground.
Risk of injury
Ensure that the wall and fixing parts used have sufficient
load-bearing capacity to be able to support the weight
of the appliance.
Furthermore please note:
- Only install the external unit outdoors, never inside a
building. Select an installation location where the external
unit will be as little exposed as possible to rain, snow or
direct insolation.
- Install the external unit where it will be as little exposed
to strong direct wind as possible, but will still be well
ventilated. Air must be able to be drawn in and blown out
unhindered. If necessary, protect against the elements with a
canopy, base and deflectors.
- Ensure that the installation location can support the
weight of the external unit and will permit installation in a
horizontal position. Furthermore, the installation floor must
be solid enough to prevent vibrations.
- You can install the external unit on solid ground or mount it
on the wall using a support panel. Subject to the wall quality,
use heavy-duty rawl plugs.
- For installation on the ground, you must factor in space for
the condensate drain and, if applicable, the depth of snow.
- Ensure that the installation location is at least 3 m from
television and radio aerials. Operation of the external unit
can lead to faults with the radio and television reception.
- Ensure that both the internal appliance and external unit
are installed in such a way that the maximum lengths and
heights of the refrigerant lines between the two devices are
not exceeded.
- When selecting the installation location, ensure that
neighbours will not be disturbed by air flow and operating
noises.
- In rented buildings, obtain the agreement of the owner.
- If you operate the external unit at low outside temperatures,
you must also follow the instructions below:
- Never install the external unit in a location where the air
inlet sides or air outlet side will be directly exposed to
draughts.
- Install the external unit with the air inlet side facing the wall,
to protect it from draughts. It is advisable to install a screen
on the air outlet side of the external unit, to offer protection
from draughts.
www.stIebel-eltron.com
5.2.1 dimensions and clearances
For trouble-free operation and further work, maintain the follow-
ing minimum clearances. In the installation location, the air must
be able to be drawn in and blown out unhindered on the air inlet
sides and the air outlet side of the external unit. For maintenance
work, you must have access to the refrigerant connections and
the control panel. Maintain the minimum dimensions to ensure
trouble-free operation.
minimum clearances
D
E
dimensions
A
m
B
m
c
m
D
m
E
m
Increase clearance "A" to 0.30 m if there is a wall to the right of
the unit.
5.3
installing the condensate drain line
Since the external unit is outside, moisture can get into it. When
operating the air conditioning system, an increased amount of
condensate may be created, especially in heating mode. In the
floor plate of the external unit, an aperture is provided to connect
a condensate drain line.
f Push the condensate drain connector provided together with
the seal in the floor plate aperture.
f connect a suitable condensate drain line to the connector.
Risk of damage
!
Insulate the condensate drain so it cannot freeze in winter.
Single-split appliances are equipped with a condensate
tray heater, which provides protection against freezing
at low outside temperatures for the condensate tray, but
not the condensate drain line.
C
single-split
multi-split
0.20
0.20
0.30
0.60
0.40
0.40
0.15
0.15
0.60
0.60
cur basIc |
19