Full adjustment
After empty adjustment the full state is to be achieved, if possible, so
that the unit switches.
The full adjustment can be repeated as often as you like. The stored
value for the empty state is not overwritten by the full adjustment.
After a new empty adjustment both values are automatically set again,
the values last defined are overwritten.
Therefore always carry out the empty adjustment first, then, if
necessary, the full adjustment!
NO/NC mode:
The switching output of the unit can be operated as normally closed
or normally open contact. To do so the unit must first be put in the
NO/NC mode.
Activating the NO/NC mode:
Press the programming pushbut-
ton for min. 10s.
The green LED first flashes slowly
(about 1Hz), after 5s more quickly
(about 2Hz), after 10s slowly again
(about 1 Hz).
12
PAGE
Press the programming pushbutton until the
green LED flashes quickly
5 ... 10 s
(= unit is in the adjustment mode).
The LED first flashes slowly (about 1 Hz), after 5s
it flashes double as quickly (about 2 Hz).
After adjustment - for the output function " nor-
mally open" - only the yellow LED lights. For the
output function "normally closed" all LEDs are
off.
min. 10 s

Werbung