Balluff Network Interface ProfiNet™
3
First Steps
3.2. Mechanical
Connection
3.3. Electrical
Connection
Supply voltage
Grounding
PROFINET
interface
www.balluff.com
The module is secured by means of two M6 screws and two washers.
Insulation support is available separately.
Pin
IN
7/8", male
Note
Where possible, use separate power supplies for sensor/bus and actuator.
Total current < 9 A The total current of all modules must not exceed 9 A even in
the case of series connection of the actuator supply.
Note
The functional ground connection between housing and machine must have a
low impedance and be as short as possible.
M12, D-coded, female
Pin
Note
Unused I/O ports must be provided with cover caps to comply with degree of
protection IP67.
Function
1
0 V
GND module / sensor and actuator supply
2
3
FE
Function earth
4
+24 V
Module / sensor supply
5
+24 V
Actuator supply
1
N24
Separate supply voltage (-)
2
0 V
GND module / sensor supply
3
FE
Function ground
4
+24 V
Module / sensor supply
5
P24
Separate supply voltage (+)
Function
1
Tx+
2
Rx+
3
Tx-
4
Rx-
Description
Transmit Data +
Receive Data +
Transmit Data -
Receive Data -