Smoke Detector Operating Manual
GB
Type: 205003
This product has been tested according to EN 14604:2005 + AC: 2008
We recommend consulting a certified specialist for smoke detectors
for the planning and installation.
1. Technology / operation
• Power supply: 9V DC Block battery
• Sound power level: ≥85 dB / 3m
• Temperature range: -10 ° C - + 40 ° C
• Humidity: ≤95% RH
• Recommended battery types: GP1604A / PAIRDEER 6LR61 / 6F22
General:
• In areas where ventilation and/or air conditioning systems are used, is must
be ensured that air movement does not affect the function of the smoke
detector.
• Smoke detectors must be permanently fixed on the ceiling. Mounting
instructions must be observed.
• Choose a mounting method that ensures a holding force of at least 20N in
vertical direction.
• The smoke detector is designed for monitoring residential buildings or
residential premises (not for industrial or commercial usage).
• A function test must be performed on each smoke detector after installation.
• The functionality of each installed smoke detector must be regularly checked
and maintenance measures must be ensured. Perform function test 1 x per
week, clean every 3 months.
• The smoke detector indicates its readiness for operation by the LED flashing
every 60 seconds.
• Smoke detectors must be taken out of service at the latest after 10 years and
replaced with a new device.
• In standard smoke detectors, the battery must be replaced annually, at the
latest however when the smoke detector reports a battery failure. Only the
battery types specified on the rating plate may be used.
2. Mounting locations
Mounting locations for smoke detectors:
• Bedrooms, children's rooms and corridors must be equipped (basic
requirement) with smoke detectors.
• Always on the ceiling
• 50cm from the wall (or beam)
• If the room is subdivided by ceiling-high furniture etc., a smoke detector must
be installed in each room partition
• In rooms with a floor area of ≤ 60m², divided into ceiling boxes by beams or
joists, the following applies:
• In ceiling boxes > 36m² a smoke detector must be installed per ceiling box
(see Figure 6a))
In rooms with a floor area of > 60m², an additional smoke detector must be
installed per 60m².
3. Planning examples
For apartments and single family homes
a) Example for use in an apartment
bathroom
kitchen
bedroom
living room
children's room
children's room
a) Example for use in a single-family home
bedroom
children's room
living room
kitchen
work room
boiler room
Minimum requirements
Optimal installation
Restricted installation
4. Arrangement in special room geometries
Following distance ratios and arrangements are recommended for detector
positioning:
a) Linear corridor
b) Rectangular corridor
c) Detector arrangement in large corridors
d) Detector arrangement in large corridors with corners
5. Constructional features
• If a room is divided in height by a podium or a gallery, a smoke detector is
required beneath these installations if the area exceeds 16m² and the length
and width exceed each 2m.
• In rooms with ceiling slopes > 20° to the horizontal, a heat pocket can form at
the top of the ceiling which prevents smoke entry into the smoke detector.
• Therefore, smoke detectors in these rooms must be mounted at least 0,5m
but not more than 1m from the ceiling top, see the following two illustrations.
Example of mounting with pedestal-shaped ceiling with a ceiling
slope > 20°
Legend
1 = smoke detector
Remarks: Smoke detectors can be attached on the position left (1) or on the
position right (2).
• In rooms with a slope ≤ 20° smoke detectors must be mounted centrally on
the ceiling.
• In ceiling boxes ≤ 36m² and with ceiling slopes ≤ 20° as well as beams or
joists with a height ≤ 0.2m, the individual ceiling boxes are not taken into
account (see Figure 6b)). Install smoke detectors as centrally as possible in
the room, in a ceiling box or on the joist.
• In these rooms have beams or ceiling joists with a height > 0.2m, the smoke
detector must be installed on a beam or girder, as centrally as possible in the
room (see section 6 Figure c).
6. Notes for ceiling installation
For ceiling with joists – (height (h) of the joist ≤ 0.20m
and an area of the ceiling box >36m² or ≤36m²)
a) Example for ceiling >36m²
Legend:
1 - Ceiling box
2 - Joist
b) Example of ceiling box ≤36m ²
Legend:
1 - Ceiling box
2 - Joist
c) Example of ceiling with joist (height (h) of the joist > 0,20m)
Legend:
1 - Ceiling box
2 - Joist
In corridors with a maximum width of 3m, the distance between two smoke
detectors may not exceed 15m. The detector distance to the front face of the
corridor must not exceed 7.5m. A detector must be arranged in crossings,
junctions and corners (mitre line) of corridors. An example of an arrangement is
shown in section 4.
7. Mounting
• Loosen the mounting plate on the rear side of the device by turning it
clockwise.
• Fix the mounting plate with the help of the enclosed mounting material to the
ceiling or wall. Check first whether the supplied mounting material is suitable
for the structural quality of the wall/ceiling.
• Insert the smoke detector in the mounting bracket and rotate the smoke
detector anti-clockwise direction until it audibly engages.
• Caution: Smoke detectors with replaceable battery can only be attached with
inserted battery because the latter have a locking mechanism.
1
ceiling
2
ceiling
Click
ceiling
ceiling
3
4
ceiling
5
Click
8. Commissioning
Remove the enclosed battery and remove the plastic film.
Connect the plug connector of the device with the battery contacts until they
audibly engage.
1
Mounting opening
Battery compartment
2
9. Functional testing
Press and hold the test button on the unit. The LED
flashes quickly and the alarm is activated after about
3 seconds. Approx. 3 seconds after the test button
is released, the smoke alarm device and is ready for
use again.
LED
Test
10. Fraud alarm / false alarms
False alarms can be triggered by the following, for example:
• welding and cutting work;
• soldering and other hot work;
• sawing and sanding work;
• dust due to construction or cleaning;
• water vapour, cooking vapours and odours;
• extreme electromagnetic influences;
• temperature fluctuations which lead to the condensation of the humidity in the
smoke detector.
In the event of works in the environment of the installed smoke detector which
trigger false alarms (e.g. renovation), the detector should be temporarily
covered or removed. After completion of the work, the original functionality of
the installed smoke detector must be restored as described in section 9.
Should the system report an alarm, please check whether the fire really exists. If
so, call the fire brigade.
If not, please check whether the mentioned reasons could have raised the
alarm. We would like to point out that we are not liable for the consequences of
false alarms. We do not cover any costs incurred by false alarms, such as from
deployment of police, fire, or key services.
11. Maintenance / cleaning
This includes at least a check of whether the smoke penetration openings are
clear (e.g. covers, contamination from fluff and dust), whether there is any
function-related damage to the smoke detector and whether the 0.5 m area
around the smoke detector is free of obstacles (such as furniture) which inhibit
fire smoke penetrating into the smoke detector. Remove the smoke detector
from the retaining plate if the smoke penetration openings are dirty. Use a
vacuum cleaner nozzle to vacuum all openings both at the periphery and back of
the housing. Then again lock the smoke detector on the retaining plate and carry
out a a functional test. Replace the smoke detector if there is any functional-
related damage to it. If the clearance around the smoke detector is insufficient,
then the mounting location must be checked and a new location determined, if
necessary.
12. WEEE-reference of disposal
In accordance with European defaults used electrical and electronics
devices may no more be given to the unsorted waste. The symbol of the
waste bin on wheels refers to the necessity of separate collection.
Please help with environmental protection and see to it that this device
is given to the for this purpose designated systems of waste sorting if
you do not use it any longer.
GUIDELINE 2012/19/EU of the EUROPEAN PARLIAMENT AND the COUNCIL of
July 04th 2012 about electrical and electronics old devices.
Batteries and accumulators are not to be disposed of in the normal
house waste bin. Every user is legally obliged, to hand over all batteries
and accumulators, irrespective of whether or not they contain harmful
substances to a communal collection point in the local town area or to
a trade dealer so that they can be disposed of in an orderly environmentally
friendly manner.
Batteries and accumulators should only be handed over when they are
completely discharged!
REV Ritter GmbH
Frankenstr. 1-4
D-63776 Mömbris
15
Service-Phone: +49 900 117-1070
1134-CPR-166
E-Mail: service@rev.biz
EN 14604:2005/AC:2008
www.rev.biz
Declaration of performance "LE 205003" available at www.rev.biz.