Telephone Helpline: 0845 146 2887 (United Kingdom)
To unlock the control panel:
Press and hold the UP
and DOWN
1.
Pon flashes on the display and the keyboard is unlocked.
2.
Note: If a button is not pressed for 10 seconds while using the control panel it times out and reverts to standby mode.
When parameters are being set the Setpoint LED will flash on the display.
Enter the Parameter Menu
Unlock the control panel, if locked.
1.
Press and hold the SET
2.
If neccessary, press the SET
3.
Alter Parameter Value
Note: Your POLAR appliance has been preset with default parameters generally deemed suitable for normal operation (see "Default
Parameter Values" on page 3). POLAR recommend these preset vlaues are used.
To alter the value, (if necessary):
With the desired parameter displayed, alter the value using the UP
1.
Press the SET
button to store the value.
2.
Note: The control panel will automatically move to the next parameter. To return to standby mode allow the control panel to time out.
Parameter Descriptions
Parameter
Name
d1
Operating temperature
d2
Temperature Differential
d3
Temperature Range
d4
Compressor Activation Time
d5
Intervals
Maximum Temperature
d6
Differential Alarm
Temperature Differential Alarm
d7
Delay
d8
Defrost Cycle Time Intervals
d9
Maximum Defrost Duration
d10
Defrost Cut-off Temperature
d11
Additional Cut-off Defrost Period
Delayed Actual Temperature
d12
Display
Compressor On/Off During
d13
Defrost
d14
Evaporator Drying Time
=19
Temperature Offset
=22
Unit of Measurement
Compressor Operation During
=23
Probe Failure
=24
Compressor 'On' Duration
=25
Compressor 'Off' Duration
=34
Initial Defrost After Startup
=38
Minimum Temperature Alarm
buttons simultaneously for 10 seconds.
button until 'd1' flashes on the display.
button repeatedly to scroll to the desired parameter (see "Parameter Descriptions" for parameter details).
Set the operating temperature of the appliance
The Temperature Differential is the allowed temperature difference above and below
the operating temperature before the compressor starts/cuts off
Set the minimum (d3) and maximum (d4) temperatures that the appliance can
fluctuate between
Enter the minimum time interval between the compressor turning off after turning on 0-999 seconds
Set an alarm to sound if the temperature inside the appliance exceeds the set
operating temperature by a specified amount
Set a delay before the temperature differential alarm is triggered
Set the time between each defrost cycle
Set the maximum length of the defrost cycle
Note: The defrost duration can be overridden by parameter d10 (below), if
the cut-off temperature is reached before the end of the defrost duration
Set the defrost cut-off temperature
Set an additional amount of defrost time after the defrost cut-off point has been
reached (if required)
Set the length of time the inner temperature of the appliance (before defrost started)
is displayed for after a defrost cycle has finished
Turn the Compressor On or Off during the defrost cycle
Set the amount of time the compressor remains turned Off after a defrost cycle,
reducing the amount of frost build up
Should there be any variance between measured and actual temperature, the
measured temperature can be offset to compensate
Set whether the temperature is displayed in Centigrade or Fahrenheit
Set whether the compressor runs or remains Off during a temperature probe failure
Set the length of time the compressor runs during a temperature probe failure
Set the length of time the compressor remains Off during a temperature probe
failure
Set whether the appliance starts a defrost cycle 10 minutes after startup or after the
time programmed in parameter d8 (Defrost Cycle Time Intervals)
Set the display to flash should the inner temperature of the appliance drop beyond a
specified point from the programmed operating temperature
and DOWN
buttons.
Description
UK
Range
(dependant on model)
-2°C to 10°C
0 to 20°C
-40°C
95°C
0°C-50°C
0-99 minutes
1-999 hours
0-999 minutes
-45°C to 50°C
0-99 minutes
0-99 minutes
On (1) or Off (0)
0-99 minutes
-20°C to 20°C
Centigrade (0) or Fahrenheit (1)
Compressor runs (1)
Remains Off until fault fixed (0)
Runs intermittently with
parameters =24 and =25 (2)
1-99 minutes
1-99 minutes
Begins 10 minutes after startup
(0) or when programmed (1)
1°C to 50°C
2