 Indoor temp set for heating
 Thermo rule setting
 Standard/Outdoor temp basis
 Cooling offset
 Heating offset
 Thermo rule setting
Set the switching method and conditions for the thermo rule.
41
42
43
 Standard/Outdoor temp basis
Set the switching method for the thermo rule.
Standard:
Outdoor temp basis: The thermostat judges based on the outdoor
 Cooling offset
 Heating offset
The thermostat judges based on the outdoor temperature and the cooling and
heating offset values.
(a) Cooling offset: The thermostat judges based on [Outdoor temp - Cooling
offset value] during cooling.
The thermostat trips ON when [Indoor temp] > [Outdoor temp - Cooling
offset value].
This value can be set in the range of 0°C to 10°C.
(b) Heating offset: The thermostat judges based on [Outdoor temp + Cooling
offset value] during heating.
The thermostat trips ON when [Indoor temp] < [Outdoor temp + Cooling
offset value].
This value can be set in the range of 0°C to 5°C.
The thermostat judges based on the indoor
temperature and set temperature.
temperature and the cooling and heating offset values.
➝ 