Herunterladen Diese Seite drucken

Siemens SENTRON 7KM9300-0AE01-0AA0 Betriebsanleitung Seite 2

Switched ethernet profinet modul
Vorschau ausblenden Andere Handbücher für SENTRON 7KM9300-0AE01-0AA0:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
SENTRON
SWITCHED ETHERNET PROFINET Module
Operating Instructions
Read and understand these instructions before installing,
operating, or maintaining the equiment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device
before working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
Important note
The products described here were developed to perform safety-oriented functions as
part of an overall installation or machine. A complete safety-oriented system gener-
ally features sensors, evaluation units, signaling units, and reliable shutdown con-
cepts. It is the responsibility of the manufacturer to ensure that a system or machine
is functioning properly as a whole. Siemens AG, its Regional Offices, and associated
companies (hereinafter referred to as "Siemens") cannot guarantee all the properties
of an overall installation or machine that has not been designed by Siemens.
Nor can Siemens assume liability for recommendations that appear or are implied in
the following description. No new guarantee, warranty, or liability claims beyond the
scope of the Siemens general terms of supply are to be derived or inferred from the
.
following description
Area of application
The SWITCHED ETHERNET PROFINET module is intended for use with PAC power
monitoring devices or COM800. The SWITCHED ETHERNET PROFINET module
integrates the PAC power monitoring device or COM800 in power management and
automation systems.
The SWITCHED ETHERNET PROFINET module
• provides the device's measured values for the PROFINET controller.
• links two Ethernet nodes via the Ethernet switch function (PROFINET IRT)
• supports Modbus TCP.
Tools required for installation
See Fig. 2.
Installation and connection
Mounting position: vertical on the device
Mount the SWITCHED ETHERNET PROFINET module before commissioning the
device. Note the following:
• ESD guidelines
• The PROFINET guidelines for installation, grounding e. t. c. - PN-Installa-
tion-Guide:
http://www.profibus.com/nc/downloads/downloads/profinet-installation-guide/dis-
play/ ;
PN Cabling Guide:
http://www.profibus.com/nc/downloads/downloads/profinet-cabling-and-intercon-
nection-technology/display/
• Use of the module is only permitted in a LAN or a segment of the LAN if all con-
nected nodes are located within one building and are supplied via a power supply
network.
Hold the SWITCHED ETHERNET PROFINET module by the plastic enclosure only.
a) Ensure safe isolation from supply.
b) Discharge yourself.
c) Mount the device.
Installation steps see Fig. 4.
(1) Connect the SWITCHED ETHERNET PROFINET module to the device. The
guide and the anti-twist element help here.
(2) Plug the RJ 45 connectors into the RJ 45–sockets.
(3) Make sure the connectors have engaged.
(4) Provide sufficient mechanical strain relief for the Ethernet cable.
2
Configuring
The SWITCHED ETHERNET PROFINET module is assigned to the
PROFINET controller using configuration software, such as STEP 7. You can find
the GSDML file required for this on the Internet (see Online Service). For COM800 the
settings can only be changed by configuration software or by using powerconfig..
Fig. 4:
Setting the language on the LCD of the SENTRON PAC
Fig. 5:
Setting the IP-configuration of the module on the LCD of the device. You
can also make these settings in the STEP 7 configuration software or in
powerconfig.
For configuration details, please refer to the following manuals:
• "PROFIBUS DPV1, SWITCHED ETHERNET PROFINET Module"
• 3VA Communication Manual.
These two manuals can be found on the CD for the Device and on the Internet (see
Online Service).
Technical data
Industrial Ethernet:
10 / 100 Mbit / s
Integral, IRT--enabled switch
Auto crossover
with 2 x 8--pin RJ 45- sockets
Auto negotiation
Power Supply
Fromdevice
Electrical isolation between the
AC 1500 V
device and the Ethernet inter-
face of the SWITCHED
ETHERNET PROFINET module
Electrical isolation between the
AC 500 V
Ethernet interface and the Ether-
net shield
Type of protection
IP20
Permissible degree of pollution
2 in accordance with IEC 61131
Weight
approx. 36 g
Dimensions of the enclosure in
63 x 43 x 22
mm (H x W x D)
Overall depth of the SWITCH ETH-
22
ERNET PROFINET module in mm
in addition to the overall depth of
the device
Housing design
VDT 3400 structure 36
Cable length
at least CAT5, < 100 m;
you can find further information at:
http://www.profibus.com/nc/downloads/downloads/
profinet-cabling-and-interconnection-technology/dis-
play/
Tolerances
in accordance with DIN 16901:1982–11
Cooling
Passive air cooling in the form of ventilation slots
Flammability class
V–0
Security information
Notice
Siemens offers IT security mechanisms for its automation and drive product portfolio
in order to support the safe operation of the plant/machine. Our products are also
continuously developed further with regard to IT security. We therefore recommend
that you keep yourself informed about updates and upgrades for our products and
always use the latest version of each product. You can find information on this at:
http://support.automation.siemens.com.
You can register for a product-specific newsletter here. For the safe operation of a
plant/machine, however, it is also necessary to integrate the automation components
into an overall IT security concept for the entire plant/machine, which corresponds to
the state-of-the-art IT technology. You can find information on this at:
http://www.siemens.com/industrialsecurity.
Products used from other manufacturers should also be taken into account here
7KM9300-0AE01-0AA0
English
Order No.: 3ZW1012-0KM03-0AA0

Werbung

loading