G
®
PREMASREG
716x - VA
The electronic PREMASREG
®
filter monitoring and liquid level detection based on pressure measurement in clean air. The devices with a housing made from stainless steel V4A,
with cable gland or M12 connector according to DIN EN 61076-2-101 and pressure port by stainless steel quick connect (pipe fitting optional) are
fitted with one switching output, one continuous output and a backlit display for setting the switching point and displaying the ACTUAL values. The
piezoresistive measuring element guarantees a high degree of reliability and accuracy.
This pressure sensor is used in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale
catering facilities, for filter monitoring and level measurement or for triggering frequency converters. The medium measured is air (non-precipitating),
or other gaseous, non-aggressive, non-combustible media. It has a manual zero point pushbutton and an offset potentiometer for final value correction.
Parameter entry is menu-based and is easy to perform using three buttons with the help of the display. The sensor is factory-calibrated; an environ-
mental precision adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
Load resistance:
Power consumption:
Measuring function:
Measuring ranges:
Type of pressure:
Pressure port:
Medium:
Media temperature:
Accuracy:
Sum of linearity+hysteresis:
Temp. drift values:
Positive ⁄ negative pressure:
Signal hysteresis:
Signal filtering:
Output:
Connection type:
Electrical connection:
Cable connection:
Housing:
Housing dimensions:
Air humidity:
Protection class:
Protection type:
Standards:
Equipment:
K factor:
Units:
Max. value displayed:
ACCESSORIES
761x - VA pressure sensor and switch is equipped with measuring functions for volume flow, differential pressure,
24 V AC ⁄ DC (± 10 %) and 15...36 V DC
R
> 5 kOhm
L
< 1.5 VA ⁄ 24 V DC, < 2.8 VA ⁄ 24 V AC
Volume flow, differential pressure, filter monitoring, fill level (adjustable)
10...100% (adjustable)
differential pressure
equipped as standard with quick connect made from stainless steel
for PVC-fabric pressure hose Ø 6 mm (external diameter)
optionally with pipe fitting, stainless steel V2A (1.4305)
for pressure lines Ø 6 mm
clean air and non-aggressive, non-combustible gases
–20...+50 °C
Type 7161 (1000 Pa): typically ± 5 Pa
Type 7165 (5000 Pa): typically ± 25 Pa
compared to the calibrated reference device
< ± 1 % of final value (pressure)
± 0.1 % ⁄ °C
max. ± 10000 Pa
± 1 % of final value (pressure) 10 Pa ⁄ 50 Pa
switchable 1 s ⁄ 10 s (via DIP switches)
and small value suppression < 1 %
0 -10 V
1 changeover contact (24 V), 1 A ohmic load
3-wire connection
0.14 - 1.5 mm², via plug-in screw terminal
cable gland, stainless steel V2A (1.4305)
(M 20 x 1.5; with strain relief, exchangeable, inner diameter 6 - 12 mm) or
M12 connector (male, 12-pin, A-code) according to DIN EN 61076-2-101
stainless steel V4A (1.4571),
with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, weather- and UV-resistant
143 x 97 x 61 mm (Tyr 2E)
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529) in the built-in state
Housing tested, TÜV SÜD, Report No. 713160960B (Skadi2)
CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
display with illumination, three-line, cutout approx. 70 x 40 mm (W x H),
for displaying the volume flow, differential pressure, contamination degree or
level and for setting the switchpoint, K factor, measuring range limits and other settings
1 to 3000 (adjustable)
m³ ⁄ s, m³ ⁄ min, m³ ⁄ h, l ⁄ s, l ⁄ min, l ⁄ h, %, cm (adjustable)
999999