Configuration of output 1
4 switching functions can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
Configuration of output 2
4 switching functions and 2 analogue signals can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
- I = analogue output 4 ... 20 mA
- U = analogue output 0 ... 10 V
Analogue start point
Measured value at which 4 mA / 0 V is provided.
ASP is active only if OU2 = I or U.
Analogue end point
Measured value at which 20 mA / 10 V is provided.
Minimum distance between ASP and AEP = 25%
(scaling factor 4).
AEP is active only if OU2 = I or U.
Setting
range
bar
PSI
MPa
1)
Measured value = displayed value * 10
2)
display -.XX = -0.XX
∆P = increments
28
All manuals and user guides at all-guides.com
ASP
min
-1.0
1)
-10
2)
-0.10
max
min
75.0
24.0
1090
350
7.50
2.40
AEP
∆P
max
100
0.1
1450
10
10.0
0.01