Herunterladen Inhalt Inhalt Diese Seite drucken

Operating Mode On Standard Operation; Safety Position; Technical Specifications - GF EA04 Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Instruction manual
3.7

Operating mode on standard operation

The actuator runs by connecting the mains voltage from the „Open" position to the
„Closed" position. By switching the mains voltage to the other input, the actuator runs from the „Closed" position to the „Open"
position. The end positions are defined by two limit switches.
3.7.1

Safety position

In case of power failure, the actuator stays in its current position.
3.8

Technical specifications

3.8.1
Specifications
Specifications
Torque
Voltages
Cycle time
Duty Cycle
L/W/H [mm]
L/W/H [inch]
Weight
Flange interface
Protection class
Accessories
Housing material
3.8.2
Dimensions EA04 10Nm
EA04
10 Nm
110 – 240V AC/ DC
24V AC/ DC
20 s/90°
75%
169/104/123
6.67/4.09/4.87
0,9 kg
F03/ 05
IP65
Limit switch mechanical
PA-GF
EA04
20 Nm
85 – 240V AC/ DC
24V AC/ DC
12 s/90°
75%
177/110/149
6.97/4.34/5.87
1,5 kg
F03/ 05
IP65
Limit switch mechanical
PA-GF
Electric Actuators Type EA04
13

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis