9 Commissioning
8. Insert the switch insert into the housing, insert
both retaining brackets to secure and press all
the way down.
9. Fit housing cover and secure it with both
screws. Make sure the wrap-around seal is
correctly located in the upper part of the hous-
ing. NOTICE: Danger of short-circuits, caused
by moisture, if the housing is not fully sealed.
10.Install the fan.
9 Commissioning
1. Check that the technical data has been ad-
hered to → Rating plate.
2. Switch the mains fuse on, perform a function
test.

10 Fault rectification

Fault rectification may only be undertaken
by a qualified electrician. Repairs may only be
carried out at the manufacturer's factory.
Fault: Control fuse of the motor protection switch
has triggered. The fan motor is separated from
the mains. A restart interlock prevents the motor
from switching back on automatically.
Cause: Exceeding the temperature permitted in
the fan's motor winding/overheating of the TB fan
thermal contacts.
Depending on the fan, wait up to 30 minutes.
Rectify the fault if the fault persists. In order to
restart, first press the red button and then the
black button, so that the black button locks into
place.
If the fan is switched back on before the
motor has cooled down, it is retriggered
within 1 minute.
11 Disassembly, environmentally-
sound disposal
Old devices and electronic components may
only be dismantled by qualified electricians.
Proper disposal avoids detrimental impact on
people and the environment and allows valuable
raw materials to be reused with the least amount
of environmental impact.
Do not dispose of electronic com-
ponents in household waste! Dis-
pose of them in an environmentally
friendly manner and recycle them at
the appropriate collection points (→
Waste Management Act).
1. Separate the components according to mater-
ial groups.
2. Dispose of packaging materials (cardboard,
filling materials, plastics) via appropriate re-
cycling systems or recycling centres.
3. Observe the respective country-specific and
local regulations.
Company information
© Maico Elektroapparate-Fabrik GmbH. Trans-
lation of the original German operating instruc-
tions. Misprints, errors and technical changes are
reserved.