3. TRANSPORT

Any damage noted after delivery of low voltage appliances must be immediately reported to the transport company.
Do not set the appliance at work. Notify the Star Progetti technical support team for all controls required.
4. VENTILATION
Distance between the heater and wall or ceiling is to be as specified in the drawing on pageS 28-29.
PLEASE NOTE: The appliance is certified for non-conductive combustible dust.
Pursuant to Italian legislative decree no. 233/03, the employer (user) is responsible for classifying the zones. Under
the employer's own responsibility, the said party must therefore check that the zone in which this heater is to be
installed corresponds to the category assigned to these heaters. The manufacturer of these heaters declines all
responsibility for any errors in this regard on the part of the customer, or for the heater if installed in another zone.
Use of the heater in normal (non-explosive) atmospheric conditions has no adverse effects on the functioning of the
heater or on workplace safety. Use of the heater in explosive atmospheric conditions in zones other than the certified
zone constitutes a grave danger to personal health and safety. This use and maintenance handbook contains
important indications regarding safety measures and special directions for transport, installation and use. Users must
read these directions before transporting, installing and setting at work. The symbols included below indicate safety
measures and supplementary instructions in these operational directions.
5. SPECIAL SAFETY INSTRUCTIONS AND GUARANTEE
To prevent damage to objects and personal injury, users must proceed strictly in accordance with the safety
measures and supplementary instructions contained in these operational directions.
PLEASE NOTE: DO NOT SET THIS HEATER AT WORK IF IT HAS BEEN DAMAGED DURINGTRANSPORT OR IN
THE PRESENCE OF VISIBLE DAMAGE. CONTACT THE MANUFACTURER FOR FURTHER INSTRUCTIONS.
MISUSE OF THESE HEATERS MAY CAUSE DAMAGE TO OBJECTS AND LEAD TO PERSONAL INJURY
All heaters must be installed and used only by qualified persons
To prevent all risks, if the supply cable is damaged, it must be replaced by the constructor.
≥ 8 Nm tightening torque of bracket adjustment screwsThe appliance is to be installed on non-combustible surfaces
The devices must be connected to an earth connection system
The components for disconnecting the devices from the power distribution network must enable complete
disconnection under overvoltage III class conditions, in compliance with the rules for installation
Appliance suitable for installation above a height of 2.0 m
The distance between the glass front and the surface to be heated must be at least 1.5 m
The appliance must not be used without the glass front
The appliance must be installed outside the normal accessibility volume
THE APPLIANCE MUST ALWAYS BE INSTALLED HORIZONTALLY
The CE mark indicates that the appliance was constructed in accordance with the EU low voltage directive