Main Switch Tripped (Xds1) - Bosch Rexroth PRC 7000 Betriebsanleitung

Schweißsteuerung
Vorschau ausblenden Andere Handbücher für Rexroth PRC 7000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

282 / 334
Bosch Rexroth AG
Assembly
7.2.12

Main switch tripped (XDS1)

Connection:
to XDS1; 14-pole,
2 rows.
Mating connector is comprised in the delivery.
Cable length:
max. 10 m at 0.75 mm
max. 75 m at 1.5 mm
Cable type:
unshielded, VDE 0281, 0812
Main switch will be tripped:
• Mains overvoltage
• Defective capacitors
• DC link-overvoltage
• Driver fault (hardware defect)
• The timer signals „Circuit breaker tripped" and
• short-circuits terminals 7 and 13 at XDS1 (change-over switch; float-
ing contact).
• There is an internal switch-off, so that an external switch-off is no
longer necessary.
If main switches with an appropriate functionality are used, this will, if
XDS1 (ncc/noc) is wired accordingly, automatically trip the main switch
and thus externally switch off the power supply.
Load:
24V
, max. 2 A
DC
No error state:
Timer detects error state:
Fig. 58: Connection terminals for main switch trip
PRC7000 |
2
2
PRC7000
XDS1
13
Device for trip­
7
ping the main
14
Terminals 14 and 7 are shorted
Terminals 7 and 13 are shorted
R911172834 / 02
switch