Radar transmitters
Vorschau ausblenden Andere Handbücher für SITRANS LR200:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 69
Device nameplate (FM/CSA)
FM Intrinsically Safe connection drawing
number A5E01003040 and CSA Intrinsically Safe connection drawing number A5E01003039
can be downloaded from the product page of our website at: www.siemens.com/LR200.
Go to Support > Installation Drawings > Level Measurement > Continuous - Radar.
• For power demands see
• For wiring requirements: follow local regulations.
• Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X /
• Refer to
• Recommended intrinsically safe barriers are listed under
Note:
about Intrinsic Safety and the application. It is the responsibility of the installer to ensure that
the intrinsically safe installation complies with both the apparatus approval requirements and
the relevant national code of practice.
Passive Shunt Diode Barriers
Note:
Manufacturer
MTL
MTL
Stahl
Stahl
How to select a passive barrier for SITRANS LR200
To make sure that the barrier safety description is suitable for the LR200 Intrinsically Safe (IS)
input parameters, carry out the following calculations:
1)
2)
A5E31993614
Downloaded from
www.Manualslib.com
Curve 1: General Purpose, Intrinsically Safe, Non-Sparking/
Energy Limited/ Non-incendive
type 4X / NEMA 6, IP67, IP68 locations.
Instructions specific to hazardous area installations
certificate listed above.
Active barriers (repeating barriers)
on page 9 and
Selecting a suitable PLC input module, power supply, or barrier requires knowledge
A well regulated supply voltage is required.
Part Number
787SP+ (Dual Channel)
7787P+ (Dual Channel)
9001/01-280-100-10 (Single Channel)
9002/01-280-110-10 (Dual Channel)
Re-e
=
max. end-to-end resistance of the barrier
Rloop
=
loop resistance (total of cable resistance plus any additional series
resistance, for example, PLC inputs and/or displays)
Vbarrier =
value of any non-linear voltage drops due to the barrier
Determine the value for Re-e from the data sheet.
Calculate the total value for Rloop.
SITRANS LR200 (HART) – QUICK START MANUAL
manuals search engine
on page 21.
Passive Shunt Diode Barriers
on page 10.
on page 12 and the ATEX
Page EN-9