Kommunikationsumsetzer

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7XV5662-0AD00
DSUB–socket
A 9-pole DSUB–socket (PC–Interface, RS232) is used for the communication between PC
and a remote protection device via CC–2M. The connection cable between the PC and
CC–2M is the standard DIGSI–communication cable 7XV5100–4. It is a non–isolated
interface and therefore it is not designed for the transmission of time–critical data.
Figure 18 DSUB–socket at the CC–2M
The following figure shows a connection plan. A gender changer is required for the opposite
side.
DIGSI
PC
Figure 19 Connection plan
Optical Fibres
The fibre–optic links (Figure 20) are provided with cover caps to prevent the ingress of dirt.
They can be removed by turning them 90° counter clockwise. When the interfaces are not
used, the cover caps shall not be removed.
FO1 / LWL1
Figure 20 Fibre–optic links for the transmission and reception directions
FO connector type:
Necessary
Fibre type:
Wavelength:
Perm. bending radii:
Note : Class 1 as defined by EN 60825–1 is met in the case of fibre types G62.5/125 µm and
G50/125 µm.
C53000-B1174-C205-1
Downloaded from
www.Manualslib.com
RS232
5
1
9
6
7XV5100-4
RS232
RS232
Cable
CC-2M
FO2 / LWL2
Rx
Tx
Rx
Tx
Receive
Send
ST–connector
Multimode FO cable
G62.5/125 µm (recommended) or G50/125 µm
λ = approx. 820 nm
for indoor cables
for outdoor cables
manuals search engine
Pin 2
Rx (input)
Pin 3
Tx (output)
Pin 5
GND
Communication
E1 / T1
E1 / T1
network
r
= 5 cm (2 in)
min
r
= 20 cm (8 in)
min
7XV5100-4
Gender
RS232
Changer
Cable
CC-2M
Warning!
Laser Radiation! Do not stare into
the beam or view directly with
optical instruments.
English
RS232
Protection
Device
41