Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - Siemens SIPART PS2 Zusatzbeschreibung

Drawer 6dr59xx mit a5e00250501...3
Vorschau ausblenden Andere Handbücher für SIPART PS2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Zusatzbeschreibung / Additional Specification

Technical Data

Technical data
General data
Travel range
(linear actuators)
Angle or rotation
(rotary actuators)
Installation
On linear actuators
On rotary actuators
Controller
Five-point switch
Dead zone
dEBA = AUTO
dEBA = 0,1 to 10%
Controllable response time
A/D converter
Scanning time
Resolution
Transmission error
Temperature influence
Degree of protection
Mounting position
76
19" – module rack
Self-adjusting
Self-adjusting or
fixed setting
=1.5 s, reduced resolution with smaller
positioning times
10 ms
≤ 0,05%
≤ 0,2%
≤ 0,1% / 10 K (...0.1%/18 °F)
IP 40 to EN 60 529
Any
7
6DR5910-0NG00-0AA0
3 to 130mm (0.12 to 5.12 inch) (angle
of feedback shaft 16 to 90°)
30 to 100°
Using mounting kit 6DR4004-8Vevtl.
and additional lever arm 6DR4004-8L
if required on actuators according to
IEC 534-6 (NAMUR) with ledge,
columns or plane surface
Using mounting kit 6DR4004-8D on
actuators with fixing platform according
to VDI/VDE 3845 and DIN 3337:
the mounting plate must be pro-vided
on the actuator side; shaft with nut and
M6 female thread (see Fig. 3-11)
IP 65 to EN 60 529 / NEMA4x
Any; in wet environment, pneumatic
connections and exhaust
opening not upwards
SIPART PS2 Zusatzbeschreibung
A5E00245544-03

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis