Expansion Valve Kit EV-.5N
Installation & Operation Manual
Additional charge of refrigerant R410A (FXN Series)
Although refrigerant has been charged into this unit, it is required that additional refrigerant be charged according to piping length.
A. Determine an additional refrigerant quantity according to the following procedure, and charge it into the system.
B. Record the additional refrigerant quantity to facilitate service activities thereafter.
Example: 3 units (expansion valve kit for wall type) + 2 units (standard indoor unit)
1. Calculating method of additional refrigerant charge (W kg)
1.1. Additional refrigerant charge calculation for liquid piping (W
See example for model RAS-10FXN, and fill in the table.
1.2. Additional refrigerant charge calculation for Indoor Unit (W
Additional refrigerant charge (1 kg/unit) of less than 8HP indoor units are not needed.
Page 4
Expansion valve kit
CH unit
Multi-kit
Pipe diameter
Total piping length (m)
(Ø mm)
22.2
(0)
9.5
(0)
5.88
(0)
2.7
(115.5)
9.53
(3+3+3+4+5+15+4+4+6+6 x 0.07 = 3.7
6.35
(5+5)
Example – Additional charge W
Pipe diameter
Total piping length (m)
(Ø mm)
22.2
9.5
5.88
2.7
9.53
6.35
This system – Additional charge W
(Example)
W2 =
0
This system
W2 =
PMML083A - 07/2008
kg)

Additional charge (kg)
x 0.39 = 0.00
x 0.28 = 0.00
x 0.9 = 0.00
x 0.2 = 3.86
x 0.03 = 0.30
:
Total = 17.87 (kg)

Additional charge (kg)
x 0.390 =
x 0.280 =
x 0.90 =
x 0.20 =
x 0.070 =
x 0.030 =
:
Total =

kg)
2
units x 1.0 kg/unit =
units x 1.0 kg/unit =
0.0
kg
kg