Corridors with a width > 3 m:
in corridors (L-/ U-shaped) with a width of more than
3 m, these should be conceptually along the flanks
and seen as individual rooms. The resulting "rooms"
must be equipped with smoke detectors accordingly.
4 a
> 3 m
4b
> 3 m
Note
Note that the requirements are not only valid for
corridors but also for rooms with these geometries
(e.g. corner rooms).
4.3.5 Standard rooms
• For pitched roofs with a roof pitch >20°, the
smoke detector must be installed at a distance
of at least 0.5 m and max. 1 m from the gable
peak, see Fig. 5a.
> 3 m
> 3 m
5 a
>20°
• Note the following for rooms that only have a par-
tial roof slope: if the horizontal ceiling is less than
1 m wide, the smoke detector must be installed
on the roof slope as shown in Figure 5b.
5b
>20°
• If the horizontal ceiling is wider than 1 m, the
smoke detector must be mounted centrally on it.
5c
>20°
• Roof pitches ≤ 20° should be treated as horizon-
tal ceilings. (See 4.3.3. Standard rooms)
0.5 m
0.5 m
max. 1 m
> 1 m
0.5 m
0.5 m
7