Quick guide temperature relay TR1200IP
1 Application and short description
Type TR1200IP temperature relays register the temperature of up to 12 sensors simultaneously and provide the
values to the electric 10 MBit/s Ethernet interface.
2 IP protocols are supported, so the registered temperatures can be subsequently evaluated by connected devices
that are linked with the TR1200IP via an Ethernet network. In motors, that could be a motor contactor, in transformers
a transformer contactor with integrated overload function and thermal monitoring.
An alarm relay reports devices and sensor errors. Sensor breaks or sensor short-circuits are also transmitted via the
protocol to the connected evaluation unit.
2 Technical data
Rated supply voltage Us:
Tolerance
Power Consumption
Ethernet interface:
Transmission speed
IP address
Subnetwork mask
UDP port
Environmental conditions:
Ambient temperature range
Storage temperature range
Altitude
Climatic conditions
Housing:
Dimensions (w x h x d)
Protection class
Weight
4 General Notes
Compliance with the following instructions is mandatory to ensure the functionality and safety of the product. If the
following instructions given especially but not limited for general safety, transport, storage, mounting, operating
conditions, start-up and disposal / recycling are not observed, the product may not operate safely and may cause a
hazard to the life and limb of users and third parties.
Deviations from the following requirements may therefore lead both to the loss of the statutory material defect liability
rights and to the liability of the buyer for the product that has become unsafe due to the deviation from the specifications.
TR1200IP
12390-0752-04
Mains Monitoring
Digital Panelmeters MINIPAN®
AC/DC 24 – 240 V, 50/60 Hz
DC 20,4 – 297 V AC 20,4 – 264 V
< 3W, < 10VA
10 MBit/s
Standard: 192.168.1.100, adjustable
Standard: 255.255.255.0, adjustable
Standard: 5000 (5001), adjustable
-20 °C ... +65 °C
-20 °C ... +70 °C
Up to 2000 m
5 – 85 % rel. humidity, no condensation
Design V4, switchgear mounting
70 x 90 x 58 mm
IP30 (housing), IP20 (terminal)
approx. 200g
Switching Relays and Controls
You can get further information and help via the
QR-Code
or search for
Datasheets, Operating Manuals and quick guides,
Connection Plans, CAD-Data, copious FAQ, Certificates.
Seite 3 / 4
ZIEHL industrie – elektronik GmbH + Co KG
Daimlerstr.13, 74523 Schwäbisch Hall, Germany
+ 49 791 504-0,
info@ziehl.de,
Measuring Transducers
Grid- and Plant Protection
updated: 2023-01-09 / dr
from Firmware: -09
TR1200IP
at ziehl.de
3 Connection Plan
www.ziehl.de
www.ziehl.de

Werbung