flammable atmospheres. Ensure that the leak detection equipment
being used is suitable for use with flammable refrigerants, i.e. no
sparking, adequately sealed or intrinsically safe.
5) Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be
available to hand. Have a dry powder orCO2 fire extinguisher adjacent
to the charging area.
6) No ignition sources
No person carrying out work in relation to a refrigeration system which
involves exposing any pipe work that contains or has contained
flammable refrigerant shall use any sources of ignition in such a
manner that it may lead to the risk of fire or explosion. All possible
ignition sources, including cigarette smoking, should be kept sufficiently
far away from the site of installation, repairing, removing and disposal,
during which flammable refrigerant can possibly be released to the
surrounding space. Prior to work taking place, the area around the
equipment is to be surveyed to make sure that there are no flammable
hazards or ignition risks. "No Smoking" signs shall be displayed.
7) Ventilated area
Ensure that the area is in the open or that it is adequately ventilated
before breaking into the system or conducting any hot work. A degree
of ventilation shall continue during the period that the work is carried
7