KONFIGURATIONSBEISPIELE EIGENSICHERER ANWENDUNGEN:
Konfigurationsbeispiel Nr. 1
Configuration example IIA - IIB and IIC
F012-P-PC-(PX)-XI-(ZB) -
TERMINAL CONNECTORS
F0-series
Supply backlight
Common ground
Main supply
Common ground
Supply *
Signal
Common ground
*Sensor supply voltage for pulse flowmeter type P : Terminal 3: 1.2 - 3.2V DC.
Please note: type PX may be used in combination with the battery (type PC).
PX will power the unit; the battery will be disabled automatically till power is disconnected.
Konfigurationsbeispiel Nr. 2
TERMINAL CONNECTORS
F0-series
Supply backlight
Common ground
Supply *
Main supply
Common ground
Supply *
Signal
Common ground
*Sensor supply voltage for pulse type P: Terminal 3: 1.2V - 3.2V DC. Terminal 6: 8.2V DC.
Please note: type PD may be used in combination with the battery (type PC). PD will power the unit; the battery will be disabled automatically till power is disconnected.
battery powered unit
HAZARDOUS AREA
Backlight option: type ZB
(not used in this example).
Basic power supply type PX:
8-30V DC
(not used in this example).
I.S. flowmeter
input type: P
pulse
Abb. 14: Konfigurationsbeispiel Eigensicherheit.
Configuration example IIA - IIB and IIC application - F012-P-PD-XI-ZB
Backlight option: type ZB
Power supply type PD: 16-30V DC
Abb. 15: Konfigurationsbeispiel Eigensicherheit.
FW-F012-P-M_v0402_04_DE.docx
SAFE AREA
HAZARDOUS AREA
I.S. flowmeter
input type: P
pulse
SAFE AREA
Uo
= max. 30 V
Power supply
= max. 200 mA
Io
For example
= max. 0,75 W
Po
MTL5025
= max. 30 V
Uo
Power supply
= max. 200 mA
Io
For example
Po
= max. 1,2 W
MTL5025
Note: above values are safety values.
Consult the technical specification for operational values.