Mounting and commissioning
NOTICE
20
Power supply control unit
Mains connection is by means of a permanently installed cable
(for example, NYM-J 3x1.5 mm²).
The control unit supply has been fused separately (maxi-
mum 16 A).
Route the mains cable through the cable gland at the left into
the control unit.
Connect the phase to terminal L and the neutral conductor to ter-
minal N.
Connect probe
Use a cable with 2 x 0.5 mm² to extend the probe cable. The maxi-
mum length of the probe cables is 50 m.
The probe cable is permanently installed and sufficiently pro-
tected from damage (for example, installed in a metal pipe).
The probe cable is not routed immediately next to or together
with cables carrying mains voltage.
Route the probe cable through the cable gland at the right into
the control unit.
Connect the probe cable to the corresponding terminals with the
designation "Sonde". Any polarity is permissible.
External unlocking
A pushbutton (normally open contact) can be connected to the two
terminals with the designation Unlock ("Entriegeln") which allows for
external unlocking of ÖWWG 3 from a distance of up to 100 m. The
maximum voltage at these terminals is 12 V. The pushbutton con-
nections must be voltage-free.
Voltage-free changeover contact
The product features a voltage-free changeover contact for transmis-
sion of the alarm condition to additional equipment (for example, ad-
ditional alarm unit ZAG 01).
The switching contact may be destroyed by voltage peaks when
inductive consumers are switched off.
Use commercially available standard RC combinations such as
0.1 µF/100 Ohm for inductive consumers.