Refrigerant piping side
770mm / 30.3" (Suspension bolt)
830mm / 32.7"(Body)
900mm / 35.4"(Ceiling opening)
950mm / 37.4"(Panel)
CAUTION
The unit body should align perfectly
with the hole. Ensure that the unit
and the hole are the same size
before moving on.
2.
(A)
Drill 4 holes 5cm (2") deep at the
ceiling hook positions in the internal
ceiling. Be sure to hold the drill at a 90°
angle to the ceiling.
(B)
Drill 4 holes 12cm-15.5cm (4.7"-6.1")
deep at the ceiling hook positions in
the internal ceiling. Be sure to hold the
drill at a 90° angle to the ceiling.
3. Using a hammer, insert the ceiling
hooks into the pre-drilled holes.
Secure the bolt using the included
washers and nuts.
4. Install the four suspension bolts.
Drain hose side
NOTE: The bottom of the unit should
be 10-18mm (0.4-0.7") (
models
models) higher than the ceiling
board. Generally, L (indicated in the
following figure) should be half the
length of the suspension bolt or long
enough to prevent the nuts from
coming off.
23
5. Mount the indoor unit. You will
need two people to lift and secure it.
Insert suspension bolts into the unit's
hanging holes. Fasten them using
the included washers and nuts.
(A)
) or 24mm (0.9") (Compact
Wall
L
10 - 18mm (0.4-0.7")
or 24mm (0.9")
Ceiling board
Super-Slim
Main body
V.2