12. Schutzfunktionen
Inverter Overload
Inverter overload prevention function is activated when the current above inverter rated current flows.
Multi-function output terminal (MO) or Multi-function relay (30AC) is used as the alarm signal output
during inverter overload trip.
Gruppe
LED Anzeige
I54
I/O Gruppe
I55
Frequency command loss
Gruppe
LED Anzeige
I16
I62
I/O Gruppe
I63
I54
I55
Select the Drive mode when frequency reference set via V1 and I or (V1+I) input terminal or communication option is lost.
I16 : This is to set the criteria for analog input signal loss when frequency reference is given by V1, I,
V1+I or Communication option.
I16
EX 1) The inverter determines that the freq reference is lost when DRV- Frq is set to 3 (Analog V1 input), I 16
to
1 and analog input signal is less than half of the minimum value set in I 7.
EX 2) The inverter determines that the freq reference is lost when DRV- Frq is set to 6 (V1+I), I 16 to 2 and V1
input signal is either below the minimum value set in I 7 or I input value is less than the I 12 value.
I62 : When no frequency command is given for the time set in I63, set the drive mode as the table
below.
I62
Elettronica Santerno S.p.A.
Via G. Di Vittorio,3 – 40020 Casalfiumanese (BO) –Italy –
Rev. A – Kapitel 12
Parameter Name
[Multi-function output terminal
select]
[Multi-function relay select]
Parameter Name
[Criteria for analog input
signal loss]
[Drive mode select after loss
of frequency command]
[Wait time after loss of
frequency command]
[Multi-function output terminal
select]
[Multi-function relay select]
[Criteria for analog
0
input signal loss]
1
2
[Drive mode select
0
after loss of
frequency
1
command]
2
www.elettronicasanterno.it
-
sales@elettronicasanterno.it
Min/Max
Einstellung
Bereich
7
0/17
7
Min/Max
Einstellung
Bereich
0
0/2
-
0/2
-
1/12
11
0/17
11
Disabled (Does not check the analog input signal loss)
When less than the value set in I 2, I 7, I 12 is entered
When below the value set in I 2, I 7, I 12 is entered
Continuous operation with the
frequency before command loss occurs
Free run stop (output cut off)
Decel to stop
SINUS N
Werks-
Einheit
einstellung
12
17
Werks-
Einheit
einstellung
0
0
1.0
Sec
12
17
Seite 5 von 6