DS
Function
A1
Auto / Manually
A2
Threshold value
A3
LED indication
A4
Restart training period
B1
Strong air current compensation
B2
Doorway
Installation above doorway?
B3
Switch off delay
B4
Sensitivity
Green potentiometer: setting the ultrasonic sensitivity (US). The ultrasonic
sensor makes the motion sensor extremely sensitive for small movements
(2–3cm). Turn the potentiometer clockwise to increase the sensitivity.
Recommended (fabric) setting: 50%.
d) Setting the switch off time (black potentiometer)
Min. 8min – max. 40min
Turn the potentiometer clockwise to increase the switch off delay. In
manual mode, the sensor operates according to the set switch off delay.
In automatic mode, the sensor increases the switch off delay during the
EN
Off
Automatic
The 3 sensor outputs operate automatically.
Auto threshold adjustment
During the training period, the sensor learns
when the detection has to be less or more
sensitive in order to switch on the lighting.
LED indication on
Saving the information
Compensation off
No
Automatic adjustment
During the training period, the sensor learns to
optimize the switch off delay, so the time during
which the lighting is switch ON can be minimized.
Automatic adjustment
During the training period, the sensor learns
when the detection has to be less or more
sensitive in order to switch on the lighting.
This in order to optimize the operation.
training period and minimizes the delay afterwards to make the time during
which te lighting is switched on as short as possible.
Recommended (fabric) setting: 25%.
e) Setting the switch off delay (timer) in test mode (8s)
1. Turn the black key to set the timer to max. (100%).
2. Turn the key to min. (0%).
3. The timer is set to 8s test mode for 1h, then automatically returns to 8min.
4. In order to manually exit the 8s test mode, turn clockwise to just above
8min.
On
Manual
-Blue output (movement) gives a continuous signal,
the lighting is switched on continuously.
-Grey output (movement + light) operates automatically.
- Potentialfree contact operates automatically.
High sensitivity
The sensor has a high degree of sensitivity to switch
on the lighting.
LED indication off
Erase all and restart training period
(on: 5s – off)
Compensation on
If the sensor is placed too close to an air current (e.g.
airco), he can mistakenly be activated. If the air current
compensation is activated, the sensor is less sensitive.
Yes
Extra sensitivity right below the sensor.
Use manual settings
The sensor operates according to the set switch off delay
(black potentiometer).
Use manual settings
The sensor operates according to the set sensitivity
(green + red potentiomete