Remote loads and local relay Settings menu

To set the operating parameters or directly switch the remote loads or local relay status, go to the
appropriate settings menu: from the load screen, press the "SET" button key for at least 5 seconds, until
the first parameter appears; the "SET" icon turns on to indicate the activation of the function.
In the SET menu, the name of the first parameter is displayed in the 3 digits at the top and its current
value in the three digits at the bottom; the
previous/next parameter, and the "SET" button key can be pressed to start changing the value of the
parameter selected.
In particular, once the "SET" push-button is pressed, the current parameter setting flashes and the
and
push-buttons can be used to go through the various parameter values; a short press on the
button keys allows "fine" regulation (in unit increments) of the value, whereas holding them down
and
results in more rapid regulation (with larger steps in the value). Once the value of the parameter has
been changed, the changed value flashes and the "SET" push-button must be pressed to save the new
setting; a TIMEOUT (10 seconds) with no user acting on the push-buttons cancels the change in the
value and the value before the change is displayed again.
To exit the settings menu, press the "SET" button key for at least 5 seconds or wait for the TIMEOUT
(30 seconds) without pressing any push-button.
The parameters for load "N" (1≤N≤10) are:
Notes:
1. The parameters for each load N are visible if:
the load has been enabled (depends on the number of remote loads enabled)
the mandatory communication objects (Load x - Slave switchover and Load x - Slave
status notification) have been connected
the enable local remote load parameter change ETS parameter has been enabled
2. Load 10 will be indicated as "L0"
N
OMINAL LOAD ABSORPTION
Allows the nominal absorption of load "N" to be set.
If the load can communicate the instantaneous power absorption, the control algorithm
ignores the nominal absorption.
VALUES: from 0.01 kW to 6.00 kW with step of 0.01 kW for fine regulation/0.10 kW for
rapid regulation, 0.80 kW (default value)
L
OAD PRIORITY
Allows the priority of load "N" to be set.
VALUES: from "2" = MAX (default for load 1) to "11" = min (default for load 10) with
step of 1
C
ONSIDER LOAD ABSORPTION BEFORE RECONNECTING IT
Allows the behaviour of the device during assessment of reconnecting load "N" to be
defined.
VALUES: Yes (1, default value), No (0)