Herunterladen Inhalt Inhalt Diese Seite drucken

Installation; Requirements For Installation; Locating The Sine Wave Inverter; Mounting The Sine Wave Inverter - Xantrex 1000i Bedienungsanleitung

Sinus wechselrichter
Vorschau ausblenden Andere Handbücher für 1000i:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

2. Installation

W
ARNING
Review the Important Safety Instructions found
at the beginning of this manual and read this
entire section, paying particular attention to the
CAUTION and WARNING statements, before
proceeding with the installation.
This section contains instructions for installing the Xantrex
Sine Wave Inverter. After securing the unit and making
wiring connections, do not turn the unit on. Proceed to
the next section of the manual which provides operating
instructions.

2.1 Requirements for Installation

C
AUTION
The Sine Wave Inverter is designed to be
permanently connected to your DC electrical
system. When Configured as an AC hardwire
version, the inverter is also designed to be
permanently connected to your AC electrical
system. To ensure adherence to proper
electrical wiring regulations, all wiring must be
done by a certified technician or electrician.
Installation Regulations: Depending on the type of
location in which you are installing the Sine Wave Inverter,
there are different codes and regulations that the
installation must meet such as your national and local
electrical codes for residential installations. Other examples
of codes and regulations for North American installations
include:
US Coast Guard and ABYC requirements for
installations on marine vessels
RV Industry Association (RVIA), CSA, and UL
requirements for installations in recreational vehicles.
It is the installer´s responsibility to ensure that all
applicable installation requirements are met.
What You Need to Install the Sine Wave Inverter
You need the following tools and hardware to properly
install the inverter:
4
English
wire stripper
mounting screws/bolts (¼" or 6mm diameter screws)
small flat blade screwdriver (for hardwire versions)
small Phillips screwdriver
wrench for DC terminals (½" or 13mm)
AC wiring for hardwire configured models (see AC
wiring section for details)
DC cables (see DC wiring section for details)
Wire connectors and crimp tool for your DC cables
AC and DC disconnects and over-current protective
devices (see section 2.4.1 for details)

2.2 Locating the Sine Wave Inverter

The inverter utilizes complex electronic circuits, and
although design precautions have been made for protection
of these circuits, they can be susceptible to damage from
use in extreme environments. The Sine Wave Inverter
should only be installed in a location that meets the
following requirements:
• Dry: do not allow water or other fluids to drip or splash
on the Sine Wave Inverter. Do not mount the inverter in
an area subject to splashing or dripping water or bilge.
• Cool: normal ambient air temperature should be between
0°C (32°F) and 25°C (77°F)—the cooler the better within
this range. Refer to the operating temperature information
in section 9 (specifications) for more details.
• Ventilated: allow at least 5 inches (13 cm) of clearance
all around the unit. Ensure the ventilation openings on the
unit are not obstructed. If mounting in a compartment,
ventilate with louvers or cut-outs.
• Safe: do not install the Sine Wave Inverter in the same
compartment as batteries or in any compartment capable
of storing flammable liquids such as gasoline. Do not
install the inverter in an engine compartment or other
location where ignition protected equipment is required.
• Dust-free: do not install the Sine Wave Inverter in a
dusty environment where either dust, wood particles or
other filings/shavings are present. These can be pulled
into the unit when the cooling fan is operating.
• Close to AC junction box: avoid the use of extended
wire lengths if possible.
• Close to battery/batteries: Avoid excessive cable
lengths but do not install the Sine Wave Inverter in the
same compartment as batteries. Use the recommended
wire lengths and sizes (see section 2.4.4). Also do not
mount the inverter where it will be exposed to the gases
produced by the battery. These gases are very corrosive
and prolonged exposure will damage the inverter.
• Protected from battery acid: never allow battery acid
to drip on the Sine Wave Inverter or its wiring when
reading specific gravity or filling the battery.

2.3 Mounting the Sine Wave Inverter

Before mounting the Sine Wave Inverter, test the chosen
location for adequate space around the unit to allow for
connections and ventilation. Mounting hardware should
be corrosion resistant and ¼" or 6mm diameter screws.
Your mounting system should be able to support three
times the weight of the inverter, which weighs
approximately 16 lbs (7.3Kg). The more clearance for
ventilation around the unit, the better the performance.
At a minimum, have 5" of free space on all sides of the
inverter.
To mount the Sine Wave Inverter
1. Mount the Sine Wave Inverter on either a horizontal
or vertical surface (such as a bulkhead) using the
mounting holes provided. For secure, permanent
Figure 1. Approved orientations for
inverter mounting
Xantrex Sine Wave Inverter Owner's Manual

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

10001800i1800Prosine 1000Prosine 1000iProsine 1800 ... Alle anzeigen

Inhaltsverzeichnis