Herunterladen Diese Seite drucken

Siemens 6ES7 305-1BA80-0AA0 Betriebsanleitung Seite 3

Simatic s7-300 outdoor dc/dc-stromversorgung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

!
Description and construction
The Outdoor Power Supply 24V/2A is a rail-mounted built-in unit. The relevant DIN/VDE regulations or equivalent local regulations must be
observed during installation.
Primary switched-mode power supply for mounting on a SIMATIC - S7 rail.
For connection to 24 / 48 / 72 / 96 / 110 V DC.
Output voltage +24V DC, potential-free, protected against short-circuit and open-circuit conditions.
Technical specifications
Input data
Input Voltage:
24 / 48 / 72 / 96 / 110V DC
Tolerance
16,8 - 138 VDC
Efficiency at full load and 24V:
>75%
Limitation of inrush current (25 C):
standard
2
20A, 5A
s
Recommended circuit breaker, ≥ 10A Charact. C.
Input current at
2,7 / 1,3 / 0,9 / 0,65 / 0,6A
Power consumption:
64W
Weight
0.75kg
1.65lb
Installation
To ensure adequate cooling, the device must be installed vertically, with the input and output terminals at the bottom. Be sure to leave a minimum
free space of 50mm ( 2in.) above and below the device.
The supply voltage (AC 120/230V) must be connected in accordance with VDE 0100 and VDE 0160. A protective device (fuse) and an isolating
device for disconnecting the power supply must be provided.
The mains switch has to be switched off and prevented from being switched on again before installation or maintenance. If these rules are
not adhered to, contact with live parts or improper use can result in death or severe personal injury.
Connections and terminal assignment
Terminals
L+1, M1
PE
L+2, M2
Siemens AG Österreich
Downloaded from
www.Manualslib.com
WARNING
Hazardous voltages are present in this electrical equipment during operation.
Failure to properly maintain the equipment can result in death, severe personal injury or substantial property damage.
Only qualified personnel is allowed to work on or around this equipment.
The successful and safe operation of this equipment is dependent on proper handling, installation and operation.
CAUTION
The device may only be opened by qualified personel.
Electrostatically sensitive device (EGB)
Output variables
DC output voltage:
24V ± 1%
Ripple content of output voltage:
<150mV
<240mV
DC output current:
0-3A
0-2A
Two devices of identical design may be connected
in parallel
24/48/72/96/110V
Environmental conditions
Temperature
Non-operating: -25 to +85 C (-13 to +185 F)
Operating:
-25 to +60 C (-13 to +140 F) Output Current 0-3A
-25 to +70 C (-13 to +158 F) Output Current 0-2A
Humidity rating: Short time Dew allowed
≤ 75% as the annual average
95% in 30 days, natural air convection cooling
1)
Function
Input voltage AC 120/230 V
Protective earth conductor
Output voltage DC 24 V
manuals search engine
ripple
ss
spikes
ss
1)
-25 C to +60 C
2)
-25 C to +70 C
2)
only at tolerance range 24-138VDC
full tolerance range 16,8-138VDC
Connected load
Remarks
2
0.5 ... 2.5mm
Screw-type terminals
22...12 AWG
Use a screwdriver with a blade width of 3.5mm (0.14in.)
Recommended tightening torque 0.5 to 0.7Nm (4.5 to 6.2lb.in.)
Protection and monitoring
functions
Current limitation:
Typ. 1.1 - 1.3I
rated
Response to short-circuit:
Automatic restart
Mains buffering time:
24/48/72/96/110V
>10ms at
line voltage and full
load
Fuse: Slow-acting
6,3A/250V
Standards and specifications
Degree of protection IP20 to IEC 529
Degree of protection 1 to IEC 536
Safety to EN60950 and EN 50178: SELV
1)
RI suppression to EN50081, limit curve A
2)
Noise immunity: EN 50082-2 Industry
EN61000-4-5
UL508 FILE E143289
Bestell-Nr.:C98130-A7537-A1-01-19
Printed in Austria
BA 02 2000
English

Werbung

loading