Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connections; Mounting - Camille Bauer SIRAX SI 815-6 Betriebsanleitung

Passiver dc-signaltrenner
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6. Electrical connections

The signal isolator SIRAX SI 815 is plugged onto a backplane
BP 902. A 96 pin connector (model C, DIN 41 612) establishes
the electrical connections between the signal isolator and the
backplane. The pin connections can be seen from Fig. 5.
Please refer to our backplane instructions for the back-
plane wiring.
Make sure that the cables are not live when
making the connections!
In the case of "Intrinsically safe" explosion-
proof versions [EEx ia] IIC, the supplementary
information given on the Type Examination
Certifi cate and also local regulations appli-
cable to electrical installations in explosion
hazard areas must be taken into account.
Note that, ...
... the required electrical insulation and trans-
mission data agree with the data on the
nameplate of the SIRAX SI 815 (
signals and
... the input and output cables should be twisted
pairs and run as far as possible away from
heavy current cables!
Connect the input and output leads E1 and E2 and A1 and
A2 according to Fig. 5.
Signal isolator with two isolation and transmission
channels
Back
b
a
c
A1
1
2
+
A
3
4
A2
+
5
B
6
7
8
C
D
E
14
F
G
20
H
I
+
K
E1
26
27
+
L
E2
28
29
30
M
31
32
14
All manuals and user guides at all-guides.com
input
output signals)!
Fig. 5.
Type 815-612.,
Standard (non-Ex)
version
and
Type 815-622.,
Ex-version,
(output signals
intrinsically safe)
E1, E2, = Input signals
A1, A2, = Output signals
6.1 Connection of the hand-held-terminals HHT
The FSK transmission versions of the signal isolators
SIRAX SI 815-6122 and SI 815-6222 can relay a frequency
modulated digital signal in both directions in addition to the
analogue signal and the auxiliary supply. Connect the hand-
held terminal HHT as shown in Figures 6 and 7.
The burden of the signalling circuit must be
as least 250 Ω. The burden is represented in
Figures 6 and 7 by the resistor R
FSK
Digital signal
2-wire
U
< 3.5 V
V
transducer
c2+
X
X
U
12 V
SI 815
A1
M
a1–
Power supply
Analog signal
U
minimum operating voltage
M
U
supply voltage
S
Fig. 6. SIRAX SI 815-6122 (only channel 1 shown),
standard (non-Ex) version,
designed for FSK communication, frequency 500 Hz ... 35 kHz.
FSK
Hazardous area
Digital signal
2-wire
U
< 8.7 V
V
transmitter
c2+
X
X
U
12 V
SI 815
A1
M
a1–
Power supply
Analog signal
U
minimum operating voltage
M
U
supply voltage
S
Fig. 7. SIRAX SI 815-6222 (only channel 1 shown),
Ex-version, (output signals A1 and A2 intrinsically safe),
designed for FSK communication, frequency 500 Hz ... 35 kHz.

7. Mounting

The signal isolator SIRAX SI 815 is plugged onto a backplane
BP 902.
When deciding where to install the signal isolator
(measuring location), take care that the limits of
the operating temperature are kept:
– 25 and + 40 °C for standard instruments
– 20 and + 40 °C for instruments in
Ex version!
.
B
Safe area
Power pack
26a+
U
24 V
E1
S
27c–
R
B
Power
supply
HHT
Safe area
Power pack
26a+
>
U
26 V
E1
S
27c–
R
B
Power
supply
HHT

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis