Location of sensor and connection cables
1a. Place the thermostat sensor cable in the sensor hose
with sealed end (not included).
1b. The sensor cable's termination may not be cov-
ered by carpets or furnishings.
3. The spiral tube and pipe are positioned beside one
another in a recess in the wall.
Make a recess in the floor opposite to where two cable
lengths will be installed. This is where the spiral tube's
termination will be located. The joint between the heating
and connection cables is also positioned in a recess so as
not to protrude through the screed layer. Do not place in the
wall or in the pipe (see image).

Installation

1. The reel bracket simplifies work. Place the reel bracket in the
perforated hole under the bottom of the package. Lift the reel
onto the reel bracket and place a weight on the package cover.
When you pull the cable, the reel will now revolve.
2. Perform the first insulation and resistance
measurement of the cable. Fill in the test
report or use Garantera on your smartphone.
06:45
Program
23
19
Just nu
Om 0:15
/ Ω
2a. The underfloor heating cable has a 2.5-metre
connection cable. It is run in a VP tube/plastic tube
designed for electrical materials.
2b. The joint for the connection cable and termination
may not be placed in or adjoining any shower spaces/
floor drains. For supplementary kits, both cold cables
must be run up and connected in parallel in the thermo-
stat.
min.
10 cm
30-60 cm
EN
min.
10 cm