Herunterladen Diese Seite drucken

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

Location of sensor and connection cables
1a. Place the thermostat sensor cable in the sensor hose
with sealed end (not included).
1b. The sensor cable's termination should not be covered
by carpets or furnishings.
3. The spiral tube and pipe are positioned beside one an-
other in a recess in the wall.
Make a recess in the floor opposite to where two cable
lengths will be installed. This is where the spiral tube's
termination will be located. The joint between the heating
and connection cables is also positioned in a recess so that
it does not protrude through the filler layer. Do not install in
the wall or in the pipe (see picture).

Installation

1. The reel bracket simplifies work. Place the reel bracket in the
perforated hole under the bottom of the package. Lift the reel
onto the reel bracket and place a weight on the package cover.
When you pull the cable, the reel will now revolve.
2. Measure the cable isolation and
resistance. Fill in the test report.
/ Ω
06:45
Program
23
19
Just nu
Om 0:15
2a. The underfloor heating cable has a 2.5-metre
connection cable. It is run in a VP-tube/plastic tube
designed for electrical materials.
2b. The joint for the connection cable and termination may
not be placed in or adjoining any shower spaces/floor
drains. For supplementary kits, both cold cables must
be run up and connected in parallel in the thermostat.
min
10 cm
30-60 cm
EN
min
10 cm
11

Werbung

loading