Deckenrauchmelder

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EN Supplement
GC 162 RWA
EN Ceiling-mounted
smoke detector
184134-00
Ceiling-mounted smoke detector GC 162 RWA
Refer to installation instructions MBZ 300, THZ and THZ Comfort,
see www.geze.com.
Technical data
Ceiling-mounted smoke
Mat. no. 184110
detector GC 162 RWA with:
à Smoke detector GC 002 D
RWA
à Base GC 160 B RWA
Colour
white, RAL 9010
Dimensions (with base, DxH)
110 mm x 54 mm
Weight
130 g
Standard
EN 54-7
Functional principle
Scatter light, adaption of the alarm
threshold, retentive
Insect grid
prevents insects getting into the meas-
uring chamber
Input voltage
24 V DC (10-30 V DC)
Input current
Static: max. 60 µA
Alarm: max. 20 mA
Installation position
Ceiling mounting
Ambient temperature
-30°C to 70°C
Alarm resistance
1.2 kΩ
Signal transmission
2-conductor technology
current increase with self-locking
Alarm reset
by key in control unit
Use
only with GEZE emergency power
supply control unit
Detector test
Alarm triggering
- using test magnet near the
magnetic sensor
- using test gas
1
Magnetic sensor for
1
testing (behind the
GEZE logo)
2
LED for
displaying state
2
Use
The GC 162 RWA is a ceiling-mounted smoke detector for use in GEZE
RWA systems.
Smoke detectors detect smoke. They work using the light scatter
principle. A light transmitter and a light receiver are arranged in the
measuring chamber in such a way that no light reaches the receiver
module in the normal case. If there are suspended particles (smoke) in
the measuring chamber, these scatter part of the light onto the receiver
module, which converts this into an electric signal.
In other words, a smoke detector not only detects smoke but all other
suspended particles and responds sensitively to soiling.
These smoke detectors work according to the principle of current increase.
In the event of an alarm, the current consumption of the detector changes.
Protection of the smoke detector from soiling
à Do not remove the dust protection cap from the smoke detector
until commissioning is about to take place.
à After the smoke detector has been installed and the dust protec-
tion removed, make sure no dust gets into the measuring chamber.
This leads to increased soiling and can significantly shorten the
service life of the smoke detector.
à The measuring chamber of a smoke detector must not be opened.
Terminating resistor for line monitoring
There must be a 10 kΩ terminating resistor built into the base GC 160 B of the
last smoke detector in a line. The resistor is included with the control unit.
Signalling
LEDs
Voltage-free
off
Normal operation
off
Alarm
on
Connection of the emergency power supply control unit MBZ300, THZ, THZ Comfort:
The maximum number of smoke or heat detectors per line depends on the control unit.
+
-
5
4
1
1
First smoke detector
2
Last smoke detector
Insert the terminal resistor in the last detector
3
4
Terminal strip GEZE emergency power supply control unit (see respective wiring diagram)
5
Smoke detector connection
Test
Use test gas from a recognised manufacturer for testing in accordance with the manufacturer's instructions
à The red LED on the detector must change to the alarm state within 40 seconds.
à An alarm must be activated on the control unit.
à After the test has been completed, reset the alarm on the control unit and carry out a detector line reset.
Current consumption
0 mA
70 μA
15-20 mA
3
2
+
-
.