Herunterladen Inhalt Inhalt Diese Seite drucken

TDK-Lambda DTM65 Produkthandbuch Seite 14

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
DTM65 Product HANDBOOK
Input Parameters:
Standard
Nominal input voltage
Input voltage range
Nominal Input frequency
Maximum input current
Input Connections: AC inlet IEC320-14 (accepts IEC320-C13)
Output Parameters:
Output channel
DTM65PW120C
DTM65PW150C
DTM65PW180C
DTM65PW240C
DTM65PW360C
DTM65PW480C
Output Connections: Kycon KPPx-4P or equivalent (see mechanical drawing below)
All individual outputs are SELV.
Note:
Non-SELV outputs are hazardous and must not be made user accessible. They must be guarded or a
deflector fitted during installation to avoid a service engineer making inadvertent contact with the output
terminals, or dropping a tool onto them.
All outputs have operational spacings to earth, and due consideration must be given to this in the end product
design.
Safety Approvals:
IEC/EN/60601-1 CB Report and Certificate.
UL/CSA 60601-1 - UL + C -UL approval
CE mark.
CE marking when applied to any DTM65-xx product, indicates compliance with the Low Voltage Directive
(2006/95/EC) in that it complies with EN60950-1, 2
60601-1
100-240VAC
90-264VAC
50-60Hz
2A
Vout (V)
Adjustment
range (V)
12
15
18
N/A
24
36
48
Page 14 of 16
Output
Maximum
current (A)
power (W)
5.0
60
4.0
60
3.6
65
2.7
65
1.8
65
1.35
65
nd
Edition
72657 issue 1, December 2011

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis