3-pt. actuator, constant Type BA-230F-, 230 V-AC operating voltage
Dimensions:
Operation:
- To reduce electricity consumption and noise, the actuator should be set to run for no longer than
120 % of the time needed for the full valve stroke.
- The closing position is self-adjusting through an automatic synchronisation function.
Synchronisation takes place when power is supplied to the unit. The zero position is calibrated once
the closing limit is reached at the valve stop point.
-The actuator can be manually operated using a 3 mm Allen key. The actuator must be disconnected
from the power supply prior to manual operation.
-The actuator has a removable cable for a 3-core electrical connection.
-The actuator is maintenance-free.
Last updated: Aug-19
Configuration:
1 - housing:
2 - emergency manual control
3 - Cable connection
4 - Threaded ring for installation M30x1.5
Specifications:
Operating voltage
Power consumption
Actuator stroke
Stroke duration
Actuator power
Ambient temperature:
Operation
Storage
Protection class
Ambient humidity
CE conformity labelled acc. following guidelines:
- EMC 2004/108/EC acc. EN 61326-1
- LVD 2006/95/EC acc. 61010-1 standard for 230
V products
Electrical Actuator connection:
B - brown
G - green
W - white
ENG
MeiFlow Shunt UD
230 V AC
0.7 VA
3.5 or 5.0 mm
18 s/mm (50) Hz
15 s/mm (60) Hz
200 N
-5 to 50 °C
-25 to 65 °C
IP 43/41
0 - 95 %
Page 12