6.3 Failure!?

A value somewhere between 70 and 80% of the capacity of your PV mod-
ule can be used as a rule of thumb for maximum possible energy generat-
ed. (The value may be lower than the above mentioned in case where it is
in the shadow or its installation has drawback.)
If the ambient temperature is high, output power may drop extremely.
If the PV inverter does not work, its error LED is on, or an error code is dis-
played, please refer to the list of countermeasures in the table below.
Display
No information is
displayed.
STANDBY    2 0 s e c
1 2 3 4 5 kWh
is displayed.
BLACKOUT
1 2 3 4 5 kWh
is displayed.
ERROR LED is on.
(Typical)
ERROR
E - 0 9
1 2 3 4 5 kWh
is displayed.
All manuals and user guides at all-guides.com
Cause
No information is
displayed on the LCD
during the night or
times when there is
little incident sunlight.
Is the DC
disconnector off?
Has there been a
blackout?
Has there been a
blackout?
Is the AC
disconnector off?
Safety device is
activated.
83
Remedy
If PV modules receive
sunlight enough, the display
shows information.
Turn on the DC disconnector.
From 2 to 5 minutes after
power has returned, the PV
inverter will start generating
power automatically.
Turn on the AC disconnector.
After 2 to 5 minutes, the PV
inverter will start generating
power without any operator
intervention.
Press and hold the POWER
switch for 2 seconds or longer
to turn off the PV inverter.
Next, press the POWER
switch for 2 seconds or longer
to restart the PV inverter. Then,
make sure that the ERROR
LED is off and no error code is
displayed after starting to run.