FOR INSTALLERS AND PROFESSIONALS
NOTE:
Must be hard wired, no plug allowed.
For your safe use in winter, it's strongly recommended to equip heating priority function.
For the detailed wiring diagram, please refer to Appendix 1.
3. Options for protecting devices and cable specification
MODEL
Rated Current A
Breaker
Rated Residual Action
Current mA
Fuse
A
2
Power Cord(mm
2
Signal cable(mm
NOTE: The above data is adapted to power cord ≤ 10m.If power cord is
increased. The signal cable can be extended to 50m at most.

2.3. Trial after installation

Please check all the wirings carefully before turning on the heat pump.
2.3.1.Inspection before use
Check installation of the whole heat pump and the pipe connections according to the pipe
connecting drawing;
Check the electric wiring according to the electrical wiring diagram and earthing connection;
Make sure that the main power is well connected;
Check if there is any obstacle in front of the air inlet and outlet of the heat pump
2.3.2.Trial
The user is advised to start the water pump before the heat pump, and turn off the heat pump
before the water pump for long life circle.
The user should start the water pump, and check for any leakage of water; Power on and press
the ON/OFF button of the heat pump, and set desired temperature in the thermostat.
In order to protect the heat pump, the heat pump is equipped with start delay function. When
starting the heat pump, the fan will start to run in 3 minutes, in another30 seconds, the
compressor will start to run.
After pool heat pump starts up, check for any abnormal noise from the heat pump.
Check the temperature setting.
7301031
7301032
7301033
12.0
15.0
30
30
12.0
15.0
3×2.5
3×2.5
3×0.5
3×0.5
7301034
7301035
19.0
22.5
30
30
19.0
22.5
3×4
3×4
3×6
3×0.5
3×0.5
3×0.5
15
7301036
7301037
24.5
28.5
11.3
30
30
30
24.5
28.5
11.3
3×6
5×2.5
3×0.5
3×0.5
10m, wire diameter must be
7301038
15.0
30
15.0
5×2.5
3×0.5

Werbung