Maintenance

Remove all dust and dirt on air filters and Lossnay cores at regular
intervals in order to prevent a deterioration in the Lossnay functions.
Removing the parts
1) Maintenance panel
Locate and remove the 4 panel fixing screws, then take off the
maintenance panel B.
Screw
Maintenance panel B
2) Lossnay cores
Take hold of the handle and draw the Lossnay cores out from the
main unit.
Lossnay cores
Handle
3) Filters
Pull off the high efficiency filters together with pre-filters.
High efficiency filters
All manuals and user guides at all-guides.com
Pre-filters
Cleaning the parts
1) Filters
Pre-filters
Use a vacuum cleaner to remove light dust. To remove stubborn
dirt wash in a mild solution of detergent and lukewarm water.
(under 40˚C)
Vacuum cleaner
Filter
CAUTION
l Never wash the filters in very hot water and never wash them
by rubbing them.
l Do not dry the filters by exposing them to a flame.
High efficiency filters
Fill the installation date in the date entry seal pasted on the new
High efficiency filter. It is useful as a guide to determine the next
replacing time required.
CAUTION
l Please exchange High efficiency filters to new ones every
one year or 3,000 hours as a guide, although they may be foul
with varied period of time.
2) Lossnay cores
Use a vacuum cleaner to suck up the dust and dirt on the exposed
surfaces of the Lossnay cores.
Use a soft brush only to clean exposed surface areas.
Do NOT wash in water.
Vacuum cleaner
(with brush attachment)
Corner
CAUTION
l Do not use the hard nozzle of the vacuum cleaner. It may
damage the exposed surfaces of the Lossnay cores.
l Under no circumstances should the Lossnay cores be
washed in water.
Assembly after maintenance
Bearing in mind the following points, assemble the parts following
the sequence for their removal in reverse.
Note
l If "FILTER" and "CLEANING" are indicated or the remote
controller, turn off the indication, after maintenance.
Lossnay core