1.0 GENERAL
The DV-14K is a time controlled relay box with
which a maximum of 4 x 600 watt fittings or
5 x 400 watt fittings can be switched. Next to
this, the DV-14K has an outlet for a heater.

1.1 TECHNICAL DATA

Dimensions
Required voltage
Max. output
Max. output heater
Isolation level
1.2 REQUIRED (ACTIVE) VOLTAGE DV-14K
To connect the DV-14K you will preferably need
a 'clean' Group of at least 15 Amp. A 'clean'
group means that this Group will be used only
by the DV-14K. If you do not have a(n) (extra)
'clean' group we recommend to have the DV-14K
installed by a certified installer.
The DV-14K has a 15 Amp thermal fuse.
This fuse turns off the DV-14K automatically in
case of an overload and / or a short circuit.
1.3 INSTALLATION OF THE DV-14K
Remove the front panel of the DV-14K housing.
At each corner of the housing you will find a
fixing hole, which you can use to insert a screw.
You can mount the housing onto a (flat) surface
with the 4 screws.
CAUTION!
The analogue timer is a sensitive part of the
DV-14K, and is not resistant to hard shocks.
DV-14K Binnenwerk PMS.indd 5
Manual DV‑14K
• Place the DV-14K close to your 'clean' group.
• Install, if needed, a grounded outlet on your
• Plug the cord into the outlet of your 'clean'
• Your DV-14K is now connected to the mains
: 210 x 290 x 90mm.
: 230 Vac / 50Hz.
1.4 CONNECTING EQUIPMENT TO THE
: 15 Ampere.
: 15 Ampere
: IP-44
You can connect 4 x 600 watt or 5 x 400 watt
fittings to your DV-14K.
In steps 1.2 and 1.3 you have;
• Connected your DV-14K to a 'clean' group,
• Mounted it onto a flat surface,
• Connected it to the mains voltage.
Now the electric ballasts (fittings) will have to
be connected to the DV-14K. Please read the
installation manual carefully before you connect
the electric ballasts, In order to connect them
properly.
If the electric ballasts has been properly
connected there will be a 230V cord on each
of the electric ballasts. Plug all the cords of
the electric ballasts into the 4 power outlets
(sockets) on the sides of the DV-14K. You now
have connected the electric ballasts to the
DV-14K.
1.5 THE HEATER OUTLET
At the front of the DV-14K you will find a (green)
built-in power outlet (socket) for the electrical
heater of max. 15 Amp. This is where you can
place your heater.
At the bottom of the DV-14K you will find a
grounded (230V) connection cord
'clean' group.
group.
voltage.
DV-14K
7