Herunterladen Inhalt Inhalt Diese Seite drucken

Unpack Filter; Configuration And Setting Of The Ventilation Level - Helios AirPal Go 300 H Montage- Und Betriebsvorschrift

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
EN
ATTENTION
ATTENTION
ATTENTION
Air purifier AirPal Go 300/600 H
5�3 Unpack filter
m
Before commissioning the air purifier AirPal Go 300/600 H for first time, it is necessary to disassemble the
filters from the set and remove the packaging / plastic from the high efficiency HEPA 14 absolute filter; it is
delivered totally protected in order to keep the filter's characteristics and properties intact (see Fig�3)
m
For any air purifier AirPal Go 300/600 H internal manipulation, is mandatory the use of suitable PPE *; mini-
mum mask and gloves� Each unit has two stickers (one on each removable filter cover) warning of the protec-
tion elements use before handling the unit� Once the filter protection has been removed, it must be placed back
into the corresponding slot (see Fig�4)
m
* In case of non-use of the PPE specified here, the absolute filter will lose its certification and filtration offe-
red, as well as the security provided by air purifier AirPal Go 300/600 H to avoid coming into direct contact with
viruses, bacteria, etc�
Easy fastening system gives easy access
for filter replacement� An allan key is
required to loosen the handle before
rotation and to tighten the handle once
access is completed�
Fig�3
m
Do not use any similar or theoretically equivalent filter without previous consultation and authorization
from the manufacturer� In case of filter manipulation or changing by non-accepted units, the filtration guaran-
tee offered by the original air purifier AirPal Go 300/600 H will be lost� See „8.4 Setup of filter replacing" for filter
replacement frequency.
5�4 Configuration and setting of the ventilation level
Preconfigured parameters of the purifier control. The user must select the setpoint depending on the area [m²] where
the unit is going to be installed. The specifications apply to a 4-way air exchange. If a higher air exchange rate is to be
achieved, a correspondingly higher volume flow in relation to the area must be set.
Air purifier AirPal Go 300 H
Surface
Q max�
(m²)
(m³/h)
7,5
100
15
200
22,5
300
30
400
37,5
500
42,5
567
m
We recommend a max. volume flow of 300 m³/h, otherwise the Hepa14 filter loses efficiency and separates less.
Fig�4
Setpoint
Control voltage
(V)
23
2,3
41
4,1
54
5,4
67
6,7
84
8,4
99
9,9
6
The H14 HEPA filter to be disassembled and
removed from their protection before com-
missioning and operation of the D (manda-
tory PPE use)�
Power
Current (A)
(W)
5,20
0,23
16,14
0,27
34,17
0,40
62,83
0,62
105,61
0,94
143,72
1,22

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Airpal go 600 h

Inhaltsverzeichnis