INSTALLATION INSTRUCTIONS Blitzductor
Installation / Montage
Special Condition
Blitzductor BXT BAS EX
BXT ML2 BD HF EX 6
IECEx DEK 11.0078X
Ex ib IIC T4/T5/T6 Gb
KEMA 06 ATEX 0274 X
II 2G Ex ib IIC T4/T5/T6 Gb
Standards:
for ATEX:
EN 60079- 0: 2012
EN 60079-11: 2012
for IECEx: IEC 60079-0: 2011
IEC 60079-11: 2011
IEC 60079-26: 2006
Connection with intrinsically safe circuits with:
Ui
= 4,2 V
Ii
= 4,8 A
Pi
= any
Ci negligibly small
Li negligibly small
Ambient temperature range:
-40°C... +55°C for temperature class T6
-40°C... +75°C for temperature class T5
-40°C... +80°C for temperature class T4
I
L
Basic circuit diagram / Prinzipschaltbild
2
1 2 3 4
1
Cable Routing / Leitungsführung
protected
protected
®
BXT ML2 BD HF EX 6
4´ 3´ 2´ 1´
Removing the module / Entfernen des Moduls
1
Page No. 1
Connection / Anschluss
max. 2.5 mm²
max. 0.4 Nm
Size 0
LifeCheck
1
2
1695 / 04.17 / 3009201
Basic circuit diagrams / Prinzipschaltbild
2
4
1 2 3 4
4´ 3´ 2´ 1´
1
3
min. 4 mm²
www. dehn-international.com
© COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016
www.dehn.de

Werbung

loading

Inhaltszusammenfassung für DEHN + SÖHNE Blitzductor BXT ML2 BD HF EX 6

  • Seite 1 INSTALLATION INSTRUCTIONS Blitzductor ® BXT ML2 BD HF EX 6 Page No. 1 1695 / 04.17 / 3009201 Installation / Montage Basic circuit diagrams / Prinzipschaltbild Special Condition Blitzductor BXT BAS EX BXT ML2 BD HF EX 6 IECEx DEK 11.0078X Ex ib IIC T4/T5/T6 Gb KEMA 06 ATEX 0274 X II 2G Ex ib IIC T4/T5/T6 Gb...
  • Seite 2 INSTALLATION INSTRUCTIONS Blitzductor BXT ML2 BD HF EX 6 ® Page No. 2 1695 / 04.17 / 3009201 Basic circuit diagrams / Prinzipschaltbilder BXT ML2 BD HF EX 6 Part No. 920 538 BXT BAS EX Part No. 920 301 2´...
  • Seite 3: Informazioni Di Sicurezza

    Überspannungsschutz DEHN + SÖHNE Hans-Dehn-Str. 1 Tel. +49 9181 906-0 1695 / 04.17 / 3009201 Page No. 3 Blitzschutz/Erdung GmbH + Co.KG. Postfach 1640 Fax +49 9181 906-1100 IEC 60417-6182: Installation, Arbeitsschutz 92306 Neumarkt info@dehn.de electrotechnical expertise DEHN schützt. Germany www.dehn.de ®...
  • Seite 4 INSTALLATION INSTRUCTIONS Blitzductor BXT ML2 BD HF EX 6 ® Page No. 4 1695 / 04.17 / 3009201 Certificates © COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016...
  • Seite 5 INSTALLATION INSTRUCTIONS Blitzductor BXT ML2 BD HF EX 6 ® Page No. 5 1695 / 04.17 / 3009201 EC/EU Declaration of Conformity Control Drawing Blitzductor Surge Protectors BXT ML2 BD HF EX 6 For use in type of protection IS, Class I Div. 1, GP A, B, C, D T4...T6, Class I, Zone 1, AEx ia[ia] IIC T4...T6 or Ex ia[ia] IIC T4...T6: Certificate CSA 13.7000011 Module input circuits (terminals X1, X2, X3 an X4) for connection to...