Electrical connection
The
DECOR-100
designed for a single phase supply, with
voltage and frequency as indicated on the
rating plate of the unit. The units are
manufactured
with
insulation (Class II) and therefore they do
not need an earth connection.
In addition to the switch shown in the
installation drawing/diagram, there must
be an All Pole switch in the fixed wiring
with a contact opening of min 3 mm.
The electrical cable must enter the
DECOR-100 through one of the cable
point (5).
Once the cable has been introduced
proceed
using
diagram applicable to the selected model.
DECOR S, C, SZ, CZ
These
models
diagrams:
Fig.3: Fan operating through the light
switch.
Fig.4:
Fan
operating
independent switch.
DECOR R, CR, RZ, CRZ
These
models
adjustable timer. The timer enables the
fan to continue running for the selected
period after the switch has been turned
off.
Fig.5:
Fan
operating
independent switch.
Fig.6: Fan operating through a light
switch
The desired run-on time is selected by
means of an adjuster positioned on the
printed
circuit
accessible once the grille (1) has been
removed:
- To reduce the run-on time, turn
anticlockwise (min. 1 minute)
is
an
extractor
double
electrical
the
electrical
use
the
following
through
are
fitted
with
through
board
(fig.
7)
- To increase the run-on time, turn
clockwise (max: 30 minutes).
DECOR H, CH, HZ, CHZ
Models provided with an electronic
humidistat which can be adjusted from
60% to 90 % RH (relative humidity) and
with a timer, adjustable between 2 and 20
minutes.
Specific recommendations
- If changing the settings of the fan you
have to handle the controls located on
the PCB. These adjusters are fragile
and must be handled with care.
- For humidity measurement is correct
we need the fan is installed in an area
where there is good air circulation.
wiring
- Do not adjust the humidity outside the
room where the vent should be
installed.
- If the humidity level is consistently
above 90% RH, the fan will not stop.
Operation
Case 1: Automatic operation (fig.8)
an
Humidistat causes
operate automatically when the humidity
level in the room is higher than the set
level. The extractor will stop automatically
an
when the humidity drops below the
selected level and after the selected
period set on the timer.
Case 2: Automatic operation as in case 1
an
with the facility to override the hygrostat
by means of the light switch (fig.6), when
the humidity level in the room is lower
than the selected level. In this case, the
extractor continues to operate for the
selected period set on the timer after the
switch light has been switched off.
and
ATENTION: When the humidity rise
above
automatic option takes precedence
over the manual and the unit cannot
then be switched off using a switch.