5 - Specifications
Nominal output
voltage
Nominal output
frequency
Output current with
linear load and
power factor 0,7
Crest factor on
output current
Nominal output
power VA
Active output power
with linear or non-
linear load P.F. 0,7
Total harmonic
distortion of output
voltage with
nominal load
Total harmonic
distortion of output
voltage with
nominal non-linear
load P.F.0,7
Overload
capacity
Number of output
phases
AC-AC conversion
efficiency with
linear load PF = 1
and charged
batteries:
•with 50% load
•with 75% load
•with 100% load
Downloaded from
www.Manualslib.com
Electrical output specifications when running on mains power
MEGALINE
1250
50 Hz / 60Hz synchronised (autosensing and/or as selected by operator)
5,37A rms
1250VA
875W
150% for 30 seconds without By-pass intervention
manuals search engine
MEGALINE
2500
230 V ± 1%
10,75A rms
3,5
2500VA
1750W
< 0,5%
< 1%
300% for 1 second without By-pass intervention
200% for 5 seconds without By-pass intervention
Single phase
80%
85%
92%
49
MEGALINE
MEGALINE
5000
3750
16,25A rms
21,6A rms
3750VA
5000VA
3500W
2625W