Programming

Planning Schedule
Enable
View/Edit
Sched. sequence
Reset
Restart
Delay
Min. autonomy
Shutdown
Delay

Tools

Segnalling Test
LCD Display Test
Battery Test
Battery Calibration
Downloaded from
www.Manualslib.com
Enable
View/Edit
Sched.
sequence
Reset
Delay
Min.
Autonomy
Delay
Signalling
Test
LCD
Display Test
Battery Test
Battery
Calibration
manuals search engine
4 - Customising the UPS operating mode
To enable or disable set programmes
To set and modify programmes. The following functions are
available:
- Batteries Test (verifies the status of the batteries)
- Batt. Calibration (calibration of the batteries)
- Turn on (to switch the UPS on)
- Turn off (to switch the UPS off)
- Absent (disables programming)
Each programme can be executed in the following ways:
- Daily "hour-minutes": executed every day at the set hour-
minutes;
- Single "day –month –hour -minutes": executed once on
the set "day –month –hour -minutes"
- Weekly "day name –hour -minutes" : executed every week
on the set "day name –hour -minutes".
Used to display all the set programmes in the daily order
(max 16)
Deletes all settings
Duration, in seconds, of the warning signal that the UPS is
about to switch back on
Percentage of battery charge below which the UPS will not
automatically switch back on
Duration, in seconds, of the warning signal that the UPS is
about to switch back on
Tests the warning lights. Press the ENTER button to
execute the test of the Green, Yellow and Red warning
lights and the Acoustic warning signal.
Tests the alphanumeric display. Press the ENTER button
and all the available digits are shown on the alphanumeric
display.
Tests the batteries. Contact your Service Centre in case of
problems.
Calibrates the batteries, calculating the discharge curve for
the batteries. We recommend this cycle be carried out
when the batteries have been changed so that the UPS is
able to provide precise information regarding the status of
their charge.