4 - Customising the UPS operating mode
Batteries
Max Time On Batt.
Max time reserve
TurnOn Test Enable
Restart Enable
External options
Setup Clock
23/06/03 -19:25:06
Monday
Operator Panel
Language
Keyboard Beep
Display Backlight
Display contrast
Password Change
Events
Log View
Log Reset
Downloaded from
www.Manualslib.com
Max Time On
Batt.
➧
Max time
reserve
TurnOn Test
Enable
Restart Enable
External options
➧
Language
➧
Keyboard Beep
Display
Backlight
Display
contrast
Password
Change
➧
Log View
Log Reset
manuals search engine
Sets the maximum time for continuous operation in
BATTERY mode, shown in seconds. If "0" is set, this
function is disabled.
Sets the maximum time for operation in BATTERY mode
after the reserve limit has been reached, shown in seconds.
If "0" is set, this function is disabled.
If enabled, the batteries are tested each time the UPS is
switched on. If disabled, the batteries are not tested when
it is switched on again.
If enabled, the UPS will switch on again when mains power
is restored after switching off due to the end of its
autonomy. If disabled, the UPS will not switch back on when
mains power is restored after switching off due to the end
of its autonomy.
Battery Chargers N°
Sets the number of external battery chargers
KB Units
Sets the number of packs of three batteries fitted externally
Sets the time and date
Select the setting to alter
Increases/Decreases the setting
Set the language
Enables or disables the acoustic signal when buttons are
pressed
Set the backlighting of the alphanumeric display
- Fixed: always lit
-Timed: the illumination switches off when the keypad has
been inactive for a few seconds
- Disabled: the illumination is always off
Sets the contrast of the display
Sets the password to access the UPS settings
Displays the events stored in the UPS memory, for example
END OF AUTONOMY, OVERHEATING ALARMS etc.. with
relative TIME and DATE
Deletes the events stored in the UPS memory
45