4 - Customising the UPS operating mode
Misc.
Int. Temp.
Ext. Temp.
Fan speed
UPS Setup
Output
Voltage
Frequency
N+x Redundancy
NB: Redundancy Settings
This function is used to manage the redundancy of the power modules. For example: a load requires N power
modules; X power modules must be added to achieve N+X redundancy.
If the load applied exceeds the power supplied by N modules during operation, the UPS will signal the lack of
redundancy
A numerical example is given below:
Load
3700
3700
1500
1000
Downloaded from
www.Manualslib.com
Int. Temp.
xx
xx
Ext. Temp.
xx
Fan speed
Voltage
Frequency
N+x
Redundancy
Power
Total
boards
power (W)
3750
3
4
5000
4
5000
5000
4
manuals search engine
Indicates the internal temperature of the UPS, shown in
Celsius
Indicates the external temperature of the UPS, shown in
Celsius
Indicates the speed of the UPS cooling fans, shown in a
percentage format (100% = maximum speed)
To set the UPS output voltage (V)
To set the UPS output frequency (Hz)
Nominal Value: to set a numerical value for the output
frequency (50 or 60)
Auto Selection:
If enabled, the UPS reads the frequency of the input
voltage and then synchronises the output to the same
value.
If disabled, the UPS uses the set Nominal Value.
To set the number of redundant boards (refer to NB:
Redundancy Settings)
Redundancy
Redundancy
alarm (W)
0
no
1
3750
2500
2
3
1250
41
Overload
alarm (W)
3750
5000
5000
5000