SHE Compact control panel EasyConnect 20A
6
Cable Lengths Diagram
Cable lengths diagram for determining the required cable cross-sections in relation to the cable length and the sum of the
drive rated currents.
6.1
Formula for calculating the cable cross-section
U = Max. voltage drop, U = 2.5 V
Note: Observe permitted current outputs, see Technical data.
2 x line length included in cable lengths diagram.
38
A = 6 mm²
A = 2 x 2.5 mm²
A = 2.5 mm²
A = 1.5 mm²
Easy-
Connect
20 A
01/13424999424