Herunterladen Diese Seite drucken

Allen-Bradley 194R-B20-1753 Installationsanleitung Seite 4

Bulletin

Werbung

*
-
- Minimum distance to grounded parts or walls
Minimaler Abstand gegen geerdete Teile oder Wände
- Distance minimale enver piéces mises à terre ou paroìs
- Distanza minimale per pezzi a massa o pareti
- Distamcia mínima a chasis o paredes
25 mm
(63/64 in.)
50 mm
(1-31/32 in.)
ø 35 mm
(1-3/8 in.) (dia.)
2x ø 5.5 mm
(2x 7/32 in.) (dia.)
*
25.4 mm
(1 in.)
min.
(UL 98/UL 508)
228 mm
(8-63/64 in.)
min.
MANUAL MOTOR CONTROLLER SHORT CIRCUIT RATINGS:
Cat. 194R-N30-1753:
5 kA rms symmetrical at 600 Vac maximum when protected by Fuses or Circuit Breakers/250 Vdc with fuses,
100 kA rms symmetrical at 600 Vac maximum when protected by J Class Fuses,
10 kA/600 Vac rms symmetrical when protected by a 140G Circuit Breaker rated 10 kA/600 Vac or 25 kA/480 Vac having an interrupting rating
of 25 kA rms, 480 Volts maximum.
Cat. 194R-N60-1753:
5 kA rms symmetrical at 600 Vac maximum when protected by Fuses or Circuit Breakers/250 Vdc with fuses,
50 kA rms symmetrical at 600 Vac maximum when protected by J Class Fuses,
10 kA/600 Vac rms symmetrical when protected by a 140G Circuit Breaker rated 10 kA/600 Vac or 25 kA/480 Vac having an interrupting rating
of 25 kA rms, 480 Volts maximum.
Cat. 194R-J30-1753; 194R-C30-1753:
Max. 200 kA rms symmetrical at 600 Vac or max. 100 kA at 250 Vdc when used with UL Listed Class J or CC fuses, 30 amperes maximum.
Cat. 194R-J60-1753:
Max. 200 kA rms symmetrical at 600 Vac or max. 100 kA at 250 Vdc when used with UL Listed Class J or Form II fuses, 60 amperes maximum.
Instruction 14-481-910-01
Artwork 14_481_910 / 09.2018 / Version 16
25.4 mm
(1 in.)
min.
76 mm
(3 in.)
(IEC 60947-3)
min.
300 mm
min.
4-M4
2.0 Nm
18lb-in
120 mm
(4-23/32 in.)
50 mm
(1-31/32 in.)
100 mm
(3-15/16 in.)
51 mm
(2 in.)
min.
(UL 98/UL 508)
248 mm
(9-3/4 in.)
min.
(IEC 60947-3)
380 mm
min.
51 mm
(2 in.)
min.
Copyright © 2018 Rockwell Automation. Technical changes reserved.
Cat. Nr.
194R-D32-1753(S)
194R-H30-1753(S)
194R-B63-1753(S)
10 mm
(25/64 in.)
194R-D63-1753(S)
194R-F63-1753(S)
194R-H60-1753(S)
194R-J60-1753(S)
194R-N60-1753
A/B
1.4 mm
4.78 mm
(1/16)
(3/16)
min.
max.
40.3 mm
(1-19/32 in.)
(UL 98/UL 508)
(IEC 60947-3)
171 mm
190 mm
(6-3/4 in.)
min.
min.
A
B
UL98/UL508
IEC60947-3
147.6 mm
165 mm
(5-13/16 in.)
111 mm
(4-3/8 in.)
45 mm
(1-49/64 in.)
min.

Werbung

loading

Diese Anleitung auch für:

194r-f25-1753194r-b32-1753194r-f32-1753194r-c30-1753194r-j30-1753194r-n30-1753 ... Alle anzeigen