Decimal place
000 setting enables display of up to 999
00.0 setting enables display of up to 99.9
0.00 setting to display up to 9.99
LED x 10: Setting multiplier for a measuring range greater than 999. In this case the function
is activated and a green LED is activated next to the display (LED x 10).
Display limit: On activation the values above and below the measuring range are not shown
in the display.
The Average Interval in Sec. is the interval in which the 16 measurements are undertaken.
In total 16 measurements are undertaken for the averaging time.
The Average Time is the interval in seconds multiplied by 16.
Fault Over Range / Fault Under Range: On activation a fault message is generated for a
measurement value outside the measuring range.
12.2.2
Digital Input DE configuration
Fig. 15
Fig. 16
The Digital Inputs can be configured as Alarm Signal and as Horn Reset. A digital input configured
to the Alarm Signal cannot be used as a Horn Reset at the same time.
Alarm Function: can be configured as output in a low or high signal (for example pressure
sensor or heat sensor with digital output).
Horn Reset: Enables the connection of an external Horn Reset.
Dräger REGARD 2400/2410
Configuration software
01833025_en.eps
01933025_de.eps
55