13. Troubleshooting guide

Expansion module does not turn on
Is the expansion module
connected to the
controller?
Is power being supplied
to the controller?
Is the cable connected
to the controller and the
expansion module?
Was the patch cable
made onsite?
Expansion module not communicating with the controller
Is the address correctly
set to a unique address?
Is the device too far
from controller?
Is there a configuration
problem?
Have the subnetwork
EOL settings been
correctly set?
Hardware input is not reading the correct value
Input wiring problem
Open circuit or short
circuit
Configuration problem
Over-voltage or over-
current at an input
Hardware output is not operating correctly
Output wiring problem
Configuration problem
16
Verify that the expansion module is connected to the controller
and that the patch cables are plugged into the connectors.
There may be no power being supplied to the controller.
Verify that the RJ-45 crimp connectors were installed on the cable
correctly. See "Subnetwork communications wiring" on page 10.
Verify that the RJ-45 crimp connectors were installed on the cable
correctly. See "Subnetwork communications wiring" on page 10.
Each expansion module must be set to a unique address for each
controller. See "Device addressing" on page 11.
Verify the distance between the expansion module and the next
and previous device on the WTC subnetwork. See "Subnetwork
communications wiring" on page 10.
Check the configuration of the expansion module; for example,
verify whether the expansion module is enabled. Refer to the
Network Communication Interface documentation for more
information.
Only the last module on the WTC subnetwork must have its EOL
termination set to ON. All other modules must have their EOL
termination set to OFF.
Check that the wiring is correct according to this manual and
according to the peripheral device's manufacturer.
Using a voltmeter, check the voltage on the input terminal. Short
circuit (0 V) and open circuit (3.3 V).
Check the configuration of the expansion module; for example,
verify whether the expansion module is enabled. Refer to the
Network Communication Interface documentation for more
information.
An over-voltage or over-current at one input can affect the
reading of other inputs. Respect the allowed voltage / current
range limits of all inputs. Consult the appropriate datasheet for
the input range limits of this expansion module.
Check that the wiring is correct according to this manual and
according to the peripheral device's manufacturer.
Check the configuration of the expansion module; for example,
verify whether the expansion module is enabled. Refer to the
Network Communication Interface documentation for more
information.